Emerson DE, VH, VE, DH Custom Alarms Only With Advanced Controls, High Head Pressure, High Humidity

Page 53

Alarm Descriptions and Solutions

6.1.3Custom Alarms (Only With Advanced Controls)

Custom alarm messages are programmed at the LCD display. The alarms may be specified by the customer at the time of order. Additional devices and wiring may be required at the factory or by oth- ers. The message displayed may be included in this alphabetical list of alarms, or it may be custom- ized text (for up to 2 alarms). If customized text is used, customer maintenance personnel should be informed of the alarm function and corrective action required.

6.1.4High Head Pressure

Compressor head pressure is monitored with a pressure-sensing switch. One SPDT pressure switch is used for the compressor in the unit. If head pressure exceeds 360 PSIG, the switch turns off the com- pressor contactor and sends an input signal to the control. When the condition is acknowledged, the alarm is silenced. However, the pressure switch in the compressor compartment of the unit must be manually reset to clear the alarm, which will allow the compressor to start.

On air cooled systems, check for power shut off to the condenser, condenser fans not working, defec- tive head pressure control valves, closed service valves, dirty condenser coils, and crimped lines. Also, make sure that when the compressor contactor is energized the side switch on the contactor closes to energize the control circuit on the air cooled condenser.

On water/glycol/GLYCOOL™ systems, check water regulating valves. Verify water/glycol flow (are pumps operating and service valves open?). Is water tower or drycooler operating? Is the coolant tem- perature entering the condenser at or below design conditions? Is relay R5 operating during cooling to turn on the drycooler?

6.1.5High Humidity

If the return air humidity has increased to the High Humidity Alarm setpoint, check the following: Is the unit setup for dehumidification (check DIP switch)? Check for proper setpoints. Does the room have a vapor barrier to seal it from outdoor humidity? Are doors or windows open to outside air? Run diagnostics to make sure the cooling system is working properly (the cooling system dehumidifies).

6.1.6High Humidity and Low Humidity (Simultaneously)

If these two alarms are displayed at the same time, the humidity input signal is lost. Dashes will be displayed for the humidity reading. The control system will deactivate humidification and dehumidi- fication. Check for a disconnected cable or a failed sensor.

6.1.7High Temperature

If the return air temperature has increased to the High Temperature Alarm setpoint, check the fol- lowing: Are the setpoints correct? Is the room load more than the unit can handle (is the unit capacity too small)? Run diagnostics to make sure all cooling components are operating (compressor and/or valves).

6.1.8High Temperature and Low Temperature (Simultaneously)

If these two alarms are displayed at the same time, the temperature input signal is lost (or the humidity is out of sensor range: 15 to 85% RH). Dashes will be displayed for the temperature reading. The control system will initiate 100% cooling. Check for a disconnected cable or a failed sensor.

6.1.9Humidifier Problem Infrared Humidifiers

This alarm is activated by the high water float switch (AM and AG controls only) in the humidifier pan assembly. The high water float switch is normally closed and opens upon alarm condition. Check for a drain clog and, if present, clean the drain. Check for float switch stuck in the on position, free or replace the switch. Check for proper operation of the humidifier water makeup valve.

Steam Generating (Canister) Humidifiers

This alarm is activated by a signal from the humidifier control indicating that the canister needs to be replaced.

45

Image 53 Contents
Liebert Deluxe System/3 Page Table of Contents Main Menu AG-Run Diagnostics Temperature Control Alarm Descriptions and SolutionsSystem Testing Figures Page Introduction System DescriptionDual Source Cooling Systems Chilled Water SystemsGlycool Chilled Glycol Cooling Systems Additional Considerations for Upflow Units Initial START-UP ProcedureDisplay the Main Menu-AM Control Advanced Microprocessor Controls SetupBasics Advanced microprocessor AM control menu Active Alarms Main Menu AM-Status/Alarm DataAlarm History Log Operating StatusSetup System Selection Main Menu AM-Setpoints/SetupDefault control and alarm setpoints Analog SensorsFunction Default Range Setup OperationSetup functions and factory default values DIP switch settings Show DIP SwitchesSelect Options Calibrate SensorsSelect Control Type Setup AlarmsAlarm Default Delay seconds Alarm default time delayHumidity Control Method Standard Alarm MessagesAnalog Setup Set Status Display Run DiagnosticsCalibrate Actuator Show InputsMain Menu AM-Date and Time Change PasswordsTest Outputs Test Control BoardControl Circuit Board Load Control FeaturesMain Menu AM-Status Display Communications DIP SwitchesNonvolatile Memory Control OutputsView/Change Functions Monitor functionsAdvanced microprocessor with graphics control panel Advanced Microprocessor with Graphics Control SetupAdvanced microprocessor with graphics AG control menu Main Menu AG-Status Display Main Menu AG-View/Set AlarmsDisplay the Main Menu-AG Control Alarm Seconds Default Time DelayStandard Custom Alarm Messages Set Up Custom AlarmsSetup Water Detect Floor Plan Installation-LT750 DIP Switch SettingsMain Menu AG-View/Set Control Setpoints Main Menu AG-Setup SystemMain Menu AG-Operating Status Auto Restart Delay Cold Start DelayDefault Settings and Ranges IR Flush Overfill infrared humidifiers onlySelect Control Algorithm Calibrate Valve ActuatorSelect Humidity Sensing Mode Main Menu AG-Run DiagnosticsShow Inputs Main Menu AG-Plot Graphs Dehumidification with Normal or Delayed ReheatMain Menu AG-Date and Time Main Menu AG-Analog/Digital Inputs Main Menu AG-View Run Hours Log Set Up Digital InputsRead Digital Inputs View 24 Hour Run Time HistoryControl Circuit Board On/Off Status Time View Only Silence Alarm Response by Control TYPE-ADVANCED Microprocessor Controls Temperature ControlDual Cooling Source Glycool CoolingChilled Water Cooling Heating Operation Electric ReheatHot Water/Steam Heat Humidity ControlDehumidification/Humidification Required, in Percent % Control Types Proportional ControlHumidification Operation System Activation Dual Cooling Source DehumidificationChilled Water Dehumidification Suggested System Tuning Procedure Intelligent Control Load Control Features Analog Sensors Connecting the Analog SensorsChanging factory-set sensor inputs Additional connections available after unit delivery Physical Connections Setup Water Detection Display Calibration View/Change Functions Alarm Descriptions and Solutions Standard AlarmsChange Filter Compressor OverloadHigh Temperature Custom Alarms Only With Advanced ControlsHigh Temperature and Low Temperature Simultaneously Humidifier Problem Infrared HumidifiersLow Temperature Loss of PowerLoss of Air Flow Low HumidityOptional/Custom Alarms Component Operation and MAINTENANCE, Checks and Adjustments System TestingEnvironmental Control Functions Proportional Heating/Cooling/ DehumidificationElectric Panel Fan Safety SwitchControl Transformer and Fuses FirestatBlower Package FiltersFan Impellers and Bearings BeltsCompressor Oil Level Refrigeration SystemElectronic Variable Speed Drive Inverter Discharge Pressure Suction PressureSuction Superheat Thermostatic Expansion Valve OperationHot Gas Bypass Valve Operation AdjustmentAir Cooled Condenser Outdoor fan/condenser configurationTesting Function of Valve Adjustment Johnson Controls/Penn Johnson valvesGlycol Solution Maintenance Water/Glycol Cooled Condensers Shell and Tube CondensersElectrical Failure Compressor ReplacementMechanical Failure Infrared Humidifier Compressor Replacement ProcedureHumidifier Changing Humidifier Lamps Autoflush Infrared Humidifier Cleaning SystemAutoflush Operation Humidifier lampsSteam generating humidifier Steam Generating HumidifierReplacing the Canister ControlsPriority Name LED Indication Description Faults-canister generator humidifierHumidifier canister part numbers Steam generating humidifier capacity Circuit Board AdjustmentsCapacity Hz Models Lbs/hr kg/hrVoltage AMP Set Pt Electric ReheatUnit Rated Rated Values Voltage Capacity Blower troubleshooting TroubleshootingChilled water troubleshooting Symptom Possible Cause Check or RemedyCompressor and refrigeration system troubleshooting Compressor and refrigeration system troubleshooting Glycol pumps troubleshooting Dehumidification troubleshootingAdjustments on Humidifier-steam generator troubleshootingReheat troubleshooting Humidifier-infrared troubleshootingMaintenance Inspection CHECKLIST-MONTHLY Maintenance Inspection CHECKLIST-SEMIANNUAL Iti Ne tTi n That