Emerson VH, DE, VE, DH manual Connecting the Analog Sensors, Changing factory-set sensor inputs

Page 48

Response by Control Type—Advanced Microprocessor Controls

5.4Analog Sensors

5.4.1Connecting the Analog Sensors

The sensor inputs are factory-set to accept a 4 - 20 mA signal. The inputs can be changed by removing the appropriate jumpers on the control circuit board. See Table 13, Figure 5 and Figure 6.

The user supplied analog sensors MUST have their own power supply. To reduce the effects of inter- ference from any noise source, the sensor input wiring should be shielded twisted pair and the shield tied to earth ground at one end.

Analog input terminals for field connections are factory wired to the microprocessor board if specified when ordered. Eight terminals are located in the field wiring compartment of the unit. Wire sensors to the terminals as follows:

Table 13 Changing factory-set sensor inputs

Terminal

Signal

41

Input #1 (+)

42

Input #1 (-)

43

Input #2 (+)

44

Input #2 (-)

45

Input #3 (+)

46

Input #3 (-)

47

Input #4 (+)

48

Input #4 (-)

Consult your Liebert supplier for a field installation kit to add these connections after, if required.

Table 14 Additional connections available after unit delivery

 

Input #1

Input #2

Input #3

Input #4

4–20 mA

Jumper P50.1&2 and

Jumper P50.5&6 and

Jumper P50.9&10 and

Jumper P50.11&14 and

P50.3&4

P50.7&8

P50.11&12

P50.15&16

 

0–5 VDC

Jumper P50.1&2

Jumper P50.5&6

Jumper P50.9&10

Jumper P50.13&14

0–10 VDC

No jumper on

No jumper on

No jumper on

No jumper on

P50.1&2 and P50.3&4

P50.5&6 and P50.7&8

P50.9&10 and P50.11&12

P50.11&12 and P50.15&16

 

Figure 5 Analog input jumpers

ENLARGED AREA

Analog input jumper location

40

Image 48 Contents
Liebert Deluxe System/3 Page Table of Contents Main Menu AG-Run Diagnostics Alarm Descriptions and Solutions Temperature ControlSystem Testing Figures Page System Description IntroductionChilled Water Systems Glycool Chilled Glycol Cooling SystemsDual Source Cooling Systems Initial START-UP Procedure Additional Considerations for Upflow UnitsAdvanced Microprocessor Controls Setup BasicsDisplay the Main Menu-AM Control Advanced microprocessor AM control menu Main Menu AM-Status/Alarm Data Active AlarmsAlarm History Log Operating StatusMain Menu AM-Setpoints/Setup Setup System SelectionDefault control and alarm setpoints Analog SensorsSetup Operation Setup functions and factory default valuesFunction Default Range Show DIP Switches DIP switch settingsSelect Options Calibrate SensorsSetup Alarms Select Control TypeAlarm default time delay Alarm Default Delay secondsStandard Alarm Messages Analog SetupHumidity Control Method Run Diagnostics Set Status DisplayCalibrate Actuator Show InputsChange Passwords Main Menu AM-Date and TimeTest Outputs Test Control BoardLoad Control Features Main Menu AM-Status DisplayControl Circuit Board DIP Switches CommunicationsNonvolatile Memory Control OutputsMonitor functions View/Change FunctionsAdvanced Microprocessor with Graphics Control Setup Advanced microprocessor with graphics control panelAdvanced microprocessor with graphics AG control menu Main Menu AG-View/Set Alarms Display the Main Menu-AG ControlMain Menu AG-Status Display Default Time Delay Alarm SecondsSet Up Custom Alarms Standard Custom Alarm MessagesSetup Water Detect Floor Plan Installation-LT750 DIP Switch SettingsMain Menu AG-Setup System Main Menu AG-Operating StatusMain Menu AG-View/Set Control Setpoints Cold Start Delay Auto Restart DelayDefault Settings and Ranges IR Flush Overfill infrared humidifiers onlyCalibrate Valve Actuator Select Control AlgorithmMain Menu AG-Run Diagnostics Select Humidity Sensing ModeShow Inputs Dehumidification with Normal or Delayed Reheat Main Menu AG-Date and TimeMain Menu AG-Plot Graphs Main Menu AG-Analog/Digital Inputs Set Up Digital Inputs Main Menu AG-View Run Hours LogRead Digital Inputs View 24 Hour Run Time HistoryControl Circuit Board On/Off Status Time View Only Silence Alarm Temperature Control Response by Control TYPE-ADVANCED Microprocessor ControlsGlycool Cooling Dual Cooling SourceChilled Water Cooling Heating Operation Electric ReheatHumidity Control Hot Water/Steam HeatDehumidification/Humidification Required, in Percent % Control Types Proportional Control Dual Cooling Source Dehumidification Chilled Water Dehumidification Humidification Operation System Activation Suggested System Tuning Procedure Intelligent Control Load Control Features Connecting the Analog Sensors Analog SensorsChanging factory-set sensor inputs Additional connections available after unit deliverySetup Water Detection DisplayPhysical Connections Calibration View/Change Functions Standard Alarms Alarm Descriptions and SolutionsChange Filter Compressor OverloadCustom Alarms Only With Advanced Controls High TemperatureHigh Temperature and Low Temperature Simultaneously Humidifier Problem Infrared HumidifiersLoss of Power Low TemperatureLoss of Air Flow Low HumidityOptional/Custom Alarms System Testing Component Operation and MAINTENANCE, Checks and AdjustmentsEnvironmental Control Functions Proportional Heating/Cooling/ DehumidificationFan Safety Switch Electric PanelControl Transformer and Fuses FirestatFilters Blower PackageFan Impellers and Bearings BeltsRefrigeration System Electronic Variable Speed Drive InverterCompressor Oil Level Suction Pressure Discharge PressureSuction Superheat Thermostatic Expansion Valve OperationAdjustment Hot Gas Bypass Valve OperationOutdoor fan/condenser configuration Air Cooled CondenserAdjustment Johnson Controls/Penn Johnson valves Testing Function of ValveGlycol Solution Maintenance Water/Glycol Cooled Condensers Shell and Tube CondensersCompressor Replacement Mechanical FailureElectrical Failure Compressor Replacement Procedure HumidifierInfrared Humidifier Autoflush Infrared Humidifier Cleaning System Changing Humidifier LampsAutoflush Operation Humidifier lampsSteam Generating Humidifier Steam generating humidifierControls Replacing the CanisterFaults-canister generator humidifier Humidifier canister part numbersPriority Name LED Indication Description Circuit Board Adjustments Steam generating humidifier capacityCapacity Hz Models Lbs/hr kg/hrElectric Reheat Unit Rated Rated Values Voltage CapacityVoltage AMP Set Pt Troubleshooting Blower troubleshootingChilled water troubleshooting Symptom Possible Cause Check or RemedyCompressor and refrigeration system troubleshooting Compressor and refrigeration system troubleshooting Dehumidification troubleshooting Glycol pumps troubleshootingHumidifier-steam generator troubleshooting Adjustments onHumidifier-infrared troubleshooting Reheat troubleshootingMaintenance Inspection CHECKLIST-MONTHLY Maintenance Inspection CHECKLIST-SEMIANNUAL Ne t ItiTi n That