Emerson VE, VH, DE, DH manual Select Control Type, Setup Alarms

Page 18

Advanced Microprocessor Controls Setup

Dehumidification with Normal or Delayed Reheat: Dehumidification with normal reheat allows for operating BOTH compressors and reheats simultaneously. It is very important that electrical ser- vice to the unit be sized and wired for this option if selected.

! CAUTION

If the electrical service to the unit is not properly sized for this option, it could trip the building circuit breakers (or fuses) or, in extreme cases, damage the building wiring.

With delayed reheat selected, the reheats are prevented from turning on when dehumidifying with both compressors until the point at which 100% heating is called for. At this time, the compressors are turned off until the reheats bring the temperature back up to the point at which the reheats are turned off.

Select Control Type

INTELLIGENT

PROPORTIONAL

TUNABLE PID

The type of system control method used by the microprocessor can be selected from the front panel. The default setting is INTELLIGENT, which approximates the actions that a human operator would take to maintain precise, stable control. The control logic uses Artificial Intelligence techniques including “fuzzy logic” and “expert systems” methods to maintain precise, stable control and increase reliability by reducing component cycles. PROPORTIONAL is a standard control method that uses one gain factor (temperature sensitivity adjustment). TUNABLE PID (Proportional, Integral, and Derivative) uses three gain factors selected by the operator. PID allows precision tuning, but requires an experienced operator and seasonal adjustments. Note that if PID is selected, it is used for temper- ature control while humidity will continue to use Proportional Control. For chilled water units with the optional Variable Speed Drive, Intelligent Control is required for proper operation.

Refer to 5.0 - Response by Control Type—Advanced Microprocessor Controls for more detail on types of control.

Setup Alarms

Selecting SETUP ALARMS will step to the following menu:

SET TIME DELAYS

ENABLE ALARMS

ENABLE COMMON ALARM

SET CUSTOM ALARMS

Each individual alarm can be programmed with a time delay from 0 to 255 seconds. Each individual alarm can be ENABLED or DISABLED and each individual alarm can be programmed to energize or not to energize the Common Alarm Relay.

Set Time Delays: By programming a time delay for an alarm, the system will delay the specified amount of time before recognizing the alarm. The alarm condition must be present for the amount of time programmed for that alarm before it will be annunciated. If the alarm condition goes away before the time delay has timed out, the alarm will not be recognized and the time delay timer will be reset. For software alarms such as Loss of Power, Short Cycle, and Low Suction Pressure, a time delay will only delay the annunciation of that alarm. The condition of the alarm is not applicable because the condition has already occurred. For these alarms the time delay should be left at the fac- tory default of 0. The following table shows the default time delays for each alarm.

10

Image 18
Contents Liebert Deluxe System/3 Page Table of Contents Main Menu AG-Run Diagnostics Alarm Descriptions and Solutions Temperature ControlSystem Testing Figures Page System Description IntroductionChilled Water Systems Glycool Chilled Glycol Cooling SystemsDual Source Cooling Systems Initial START-UP Procedure Additional Considerations for Upflow UnitsAdvanced Microprocessor Controls Setup BasicsDisplay the Main Menu-AM Control Advanced microprocessor AM control menu Alarm History Log Main Menu AM-Status/Alarm DataActive Alarms Operating StatusDefault control and alarm setpoints Main Menu AM-Setpoints/SetupSetup System Selection Analog SensorsSetup Operation Setup functions and factory default valuesFunction Default Range Select Options Show DIP SwitchesDIP switch settings Calibrate SensorsSetup Alarms Select Control TypeAlarm default time delay Alarm Default Delay secondsStandard Alarm Messages Analog SetupHumidity Control Method Calibrate Actuator Run DiagnosticsSet Status Display Show InputsTest Outputs Change PasswordsMain Menu AM-Date and Time Test Control BoardLoad Control Features Main Menu AM-Status DisplayControl Circuit Board Nonvolatile Memory DIP SwitchesCommunications Control OutputsMonitor functions View/Change FunctionsAdvanced Microprocessor with Graphics Control Setup Advanced microprocessor with graphics control panelAdvanced microprocessor with graphics AG control menu Main Menu AG-View/Set Alarms Display the Main Menu-AG ControlMain Menu AG-Status Display Default Time Delay Alarm SecondsSetup Water Detect Floor Plan Set Up Custom AlarmsStandard Custom Alarm Messages Installation-LT750 DIP Switch SettingsMain Menu AG-Setup System Main Menu AG-Operating StatusMain Menu AG-View/Set Control Setpoints Default Settings and Ranges Cold Start DelayAuto Restart Delay IR Flush Overfill infrared humidifiers onlyCalibrate Valve Actuator Select Control AlgorithmMain Menu AG-Run Diagnostics Select Humidity Sensing ModeShow Inputs Dehumidification with Normal or Delayed Reheat Main Menu AG-Date and TimeMain Menu AG-Plot Graphs Main Menu AG-Analog/Digital Inputs Read Digital Inputs Set Up Digital InputsMain Menu AG-View Run Hours Log View 24 Hour Run Time HistoryControl Circuit Board On/Off Status Time View Only Silence Alarm Temperature Control Response by Control TYPE-ADVANCED Microprocessor ControlsChilled Water Cooling Glycool CoolingDual Cooling Source Heating Operation Electric ReheatDehumidification/Humidification Required, in Percent % Humidity ControlHot Water/Steam Heat Control Types Proportional ControlDual Cooling Source Dehumidification Chilled Water DehumidificationHumidification Operation System Activation Suggested System Tuning Procedure Intelligent Control Load Control Features Changing factory-set sensor inputs Connecting the Analog SensorsAnalog Sensors Additional connections available after unit deliverySetup Water Detection DisplayPhysical Connections Calibration View/Change Functions Change Filter Standard AlarmsAlarm Descriptions and Solutions Compressor OverloadHigh Temperature and Low Temperature Simultaneously Custom Alarms Only With Advanced ControlsHigh Temperature Humidifier Problem Infrared HumidifiersLoss of Air Flow Loss of PowerLow Temperature Low HumidityOptional/Custom Alarms Environmental Control Functions System TestingComponent Operation and MAINTENANCE, Checks and Adjustments Proportional Heating/Cooling/ DehumidificationControl Transformer and Fuses Fan Safety SwitchElectric Panel FirestatFan Impellers and Bearings FiltersBlower Package BeltsRefrigeration System Electronic Variable Speed Drive InverterCompressor Oil Level Suction Superheat Suction PressureDischarge Pressure Thermostatic Expansion Valve OperationAdjustment Hot Gas Bypass Valve OperationOutdoor fan/condenser configuration Air Cooled CondenserGlycol Solution Maintenance Adjustment Johnson Controls/Penn Johnson valvesTesting Function of Valve Water/Glycol Cooled Condensers Shell and Tube CondensersCompressor Replacement Mechanical FailureElectrical Failure Compressor Replacement Procedure HumidifierInfrared Humidifier Autoflush Operation Autoflush Infrared Humidifier Cleaning SystemChanging Humidifier Lamps Humidifier lampsSteam Generating Humidifier Steam generating humidifierControls Replacing the CanisterFaults-canister generator humidifier Humidifier canister part numbersPriority Name LED Indication Description Capacity Circuit Board AdjustmentsSteam generating humidifier capacity Hz Models Lbs/hr kg/hrElectric Reheat Unit Rated Rated Values Voltage CapacityVoltage AMP Set Pt Chilled water troubleshooting TroubleshootingBlower troubleshooting Symptom Possible Cause Check or RemedyCompressor and refrigeration system troubleshooting Compressor and refrigeration system troubleshooting Dehumidification troubleshooting Glycol pumps troubleshootingHumidifier-steam generator troubleshooting Adjustments onHumidifier-infrared troubleshooting Reheat troubleshootingMaintenance Inspection CHECKLIST-MONTHLY Maintenance Inspection CHECKLIST-SEMIANNUAL Ti n Ne tIti That

VE, DH, VH, DE specifications

Emerson is a well-known brand in the field of automation solutions, offering a range of products that cater to various industries. Among its diverse portfolio, Emerson’s products like DE (Digital Electronics), VH (Variable Frequency Drives), DH (Distributed Control Systems), and VE (Valve Positioners) stand out for their advanced features, cutting-edge technologies, and unique characteristics.

Digital Electronics (DE) from Emerson represents the backbone of modern automation systems. These devices are characterized by their highly reliable digital communication capabilities, providing robust solutions for process monitoring and control. DE products integrate seamlessly with various automation platforms, allowing for easy data exchange and system interoperability. The advanced analytics embedded in these systems enable predictive maintenance strategies, enhancing overall operational efficiency.

Variable Frequency Drives (VH) are integral to motor control technologies, maximizing energy efficiency in various applications. Emerson's VH drives are designed for flexibility, supporting multiple motor types and configurations. These drives utilize pulse width modulation (PWM) technology, allowing for precise speed control and improved application performance. Their built-in protection features help extend motor life, prevent downtime, and reduce maintenance costs. Furthermore, the user-friendly interfaces of VH drives facilitate quick setup and troubleshooting.

Distributed Control Systems (DH) from Emerson provide a holistic approach to managing complex industrial processes. They enable centralized control while ensuring that local operations continue seamlessly. DH systems are characterized by their modular architecture, making them highly scalable and adaptable to changing operational needs. Advanced control algorithms within these systems help optimize processes, ensuring maximum productivity. Additionally, their enhanced cybersecurity features protect critical industrial operations from potential threats.

Emerson's Valve Positioners (VE) play a crucial role in regulating flow and pressure in various processes. These devices provide precise positioning capabilities, enhancing the performance of control valves. The VE systems incorporate smart technologies such as adaptive control and diagnostics, allowing them to self-tune and deliver accurate performance over time. Their compact design and robust build ensure they operate effectively in challenging environments.

In summary, Emerson's DE, VH, DH, and VE offerings embody the latest innovations in automation technology. Their main features, including digital communication, energy efficiency, scalability, and precision control, cater to the diverse demands of modern industries. With these products, Emerson not only enhances operational efficiency but also paves the way for intelligent automation solutions that are crucial for the future of industrial processes.