Emerson DH Refrigeration System, Electronic Variable Speed Drive Inverter, Compressor Oil Level

Page 59

Component Operation and Maintenance, Checks and Adjustments

7.3.3Electronic Variable Speed Drive (Inverter)

On large Deluxe chilled water models an optional variable speed drive inverter is available. This packaged unit is factory set and should not require field adjustments. The variable speed drive saves power by reducing blower speed to match unit load. If you suspect a problem with the inverter, first make sure that the INTELLIGENT CONTROL method is selected at the microprocessor.

! WARNING

For operator safety, the variable speed drive must not be programmed while power is connected to the motor.

Read all instructions before proceeding.

Only qualified service technicians should make changes to the variable speed drive programming.

1.TURN OFF ALL POWER TO THE UNIT AT THE DISCONNECT.

2.Open the unit accent panel and electric box cover.

3.Find the main fan motor wires. These are connected to the motor overload relay in the high-voltage section of the electric box.

a.Mark motor wires to ensure they can be reconnected in the same order.

b.Disconnect motor wires at the load side of the motor overload relay.

c.Close the electric box cover.

4.Remove the right front vertical panel to gain access to the variable speed drive.

5.With the panel removed, restore power to the unit by turning the disconnect on.

6.Consult the factory for instructions on unlocking the keypad—the keypad is locked after factory programming of the variable speed drive parameters.

7.Consult the variable speed drive operation manual for instructions on accessing and changing the desired parameter settings.

8.Place the right front vertical panel back on the unit.

9.Reconnect the motor wires to the overload and close the electric box cover and unit accent panel.

10.Restore power at the disconnect

7.4Refrigeration System

Each month the components of the refrigeration system should be inspected for proper function and signs of wear. Because evidence of malfunction is usually present prior to component failure, periodic inspections can be a major factor in the prevention of most system failures.

Refrigerant lines must be properly supported and not allowed to vibrate against ceilings, floors, or the unit frame. Inspect all refrigerant lines every six months for signs of wear and proper support. Also inspect capillary and equalizer lines from the expansion valve and support as necessary.

Each liquid line has a sight glass that indicates liquid refrigerant flow and the presence of moisture. Bubbles in the sight glass indicate a shortage of refrigerant or a restriction in the liquid line. The moisture indicator changes from green to yellow when moisture is present in the system.

7.4.1Compressor Oil Level

There is a glass “bull’s eye” provided on each compressor (clearly visible when the end door is open) that permits viewing the oil level.

Normally, the oil level should be 1/2 to 3/4 up from the bottom of the sight glass. However, this level may vary during operation due to the action of the moving parts. When idle, the oil level may be higher due to absorption of the refrigerant.

After a compressor has been idle for an extended length of time, foaming will usually be present when the compressor first starts. Wait until the compressor has been operating for at least five minutes before viewing the oil level.

Refrigeration oil does not deteriorate with normal usage and does not need to be changed unless it becomes discolored or acidic. Periodically inspect the compressor compartment for signs of oil leakage. If a leak is present, it must be corrected and the oil level returned to its proper level using Sunisco 3GS refrigerant oil. Take new oil from sealed containers opened at the time of use. Oil exposed to air will absorb moisture.

51

Image 59
Contents Liebert Deluxe System/3 Page Table of Contents Main Menu AG-Run Diagnostics Temperature Control Alarm Descriptions and SolutionsSystem Testing Figures Page Introduction System DescriptionDual Source Cooling Systems Chilled Water SystemsGlycool Chilled Glycol Cooling Systems Additional Considerations for Upflow Units Initial START-UP ProcedureDisplay the Main Menu-AM Control Advanced Microprocessor Controls SetupBasics Advanced microprocessor AM control menu Operating Status Main Menu AM-Status/Alarm DataActive Alarms Alarm History LogAnalog Sensors Main Menu AM-Setpoints/SetupSetup System Selection Default control and alarm setpointsFunction Default Range Setup OperationSetup functions and factory default values Calibrate Sensors Show DIP SwitchesDIP switch settings Select OptionsSelect Control Type Setup AlarmsAlarm Default Delay seconds Alarm default time delayHumidity Control Method Standard Alarm MessagesAnalog Setup Show Inputs Run DiagnosticsSet Status Display Calibrate ActuatorTest Control Board Change PasswordsMain Menu AM-Date and Time Test OutputsControl Circuit Board Load Control FeaturesMain Menu AM-Status Display Control Outputs DIP SwitchesCommunications Nonvolatile MemoryView/Change Functions Monitor functionsAdvanced microprocessor with graphics control panel Advanced Microprocessor with Graphics Control SetupAdvanced microprocessor with graphics AG control menu Main Menu AG-Status Display Main Menu AG-View/Set AlarmsDisplay the Main Menu-AG Control Alarm Seconds Default Time DelayInstallation-LT750 DIP Switch Settings Set Up Custom AlarmsStandard Custom Alarm Messages Setup Water Detect Floor PlanMain Menu AG-View/Set Control Setpoints Main Menu AG-Setup SystemMain Menu AG-Operating Status IR Flush Overfill infrared humidifiers only Cold Start DelayAuto Restart Delay Default Settings and RangesSelect Control Algorithm Calibrate Valve ActuatorSelect Humidity Sensing Mode Main Menu AG-Run DiagnosticsShow Inputs Main Menu AG-Plot Graphs Dehumidification with Normal or Delayed ReheatMain Menu AG-Date and Time Main Menu AG-Analog/Digital Inputs View 24 Hour Run Time History Set Up Digital InputsMain Menu AG-View Run Hours Log Read Digital InputsControl Circuit Board On/Off Status Time View Only Silence Alarm Response by Control TYPE-ADVANCED Microprocessor Controls Temperature ControlHeating Operation Electric Reheat Glycool CoolingDual Cooling Source Chilled Water CoolingControl Types Proportional Control Humidity ControlHot Water/Steam Heat Dehumidification/Humidification Required, in Percent %Humidification Operation System Activation Dual Cooling Source DehumidificationChilled Water Dehumidification Suggested System Tuning Procedure Intelligent Control Load Control Features Additional connections available after unit delivery Connecting the Analog SensorsAnalog Sensors Changing factory-set sensor inputsPhysical Connections SetupWater Detection Display Calibration View/Change Functions Compressor Overload Standard AlarmsAlarm Descriptions and Solutions Change FilterHumidifier Problem Infrared Humidifiers Custom Alarms Only With Advanced ControlsHigh Temperature High Temperature and Low Temperature SimultaneouslyLow Humidity Loss of PowerLow Temperature Loss of Air FlowOptional/Custom Alarms Proportional Heating/Cooling/ Dehumidification System TestingComponent Operation and MAINTENANCE, Checks and Adjustments Environmental Control FunctionsFirestat Fan Safety SwitchElectric Panel Control Transformer and FusesBelts FiltersBlower Package Fan Impellers and BearingsCompressor Oil Level Refrigeration SystemElectronic Variable Speed Drive Inverter Thermostatic Expansion Valve Operation Suction PressureDischarge Pressure Suction SuperheatHot Gas Bypass Valve Operation AdjustmentAir Cooled Condenser Outdoor fan/condenser configurationWater/Glycol Cooled Condensers Shell and Tube Condensers Adjustment Johnson Controls/Penn Johnson valvesTesting Function of Valve Glycol Solution MaintenanceElectrical Failure Compressor ReplacementMechanical Failure Infrared Humidifier Compressor Replacement ProcedureHumidifier Humidifier lamps Autoflush Infrared Humidifier Cleaning SystemChanging Humidifier Lamps Autoflush OperationSteam generating humidifier Steam Generating HumidifierReplacing the Canister ControlsPriority Name LED Indication Description Faults-canister generator humidifierHumidifier canister part numbers Hz Models Lbs/hr kg/hr Circuit Board AdjustmentsSteam generating humidifier capacity CapacityVoltage AMP Set Pt Electric ReheatUnit Rated Rated Values Voltage Capacity Symptom Possible Cause Check or Remedy TroubleshootingBlower troubleshooting Chilled water troubleshootingCompressor and refrigeration system troubleshooting Compressor and refrigeration system troubleshooting Glycol pumps troubleshooting Dehumidification troubleshootingAdjustments on Humidifier-steam generator troubleshootingReheat troubleshooting Humidifier-infrared troubleshootingMaintenance Inspection CHECKLIST-MONTHLY Maintenance Inspection CHECKLIST-SEMIANNUAL That Ne tIti Ti n

VE, DH, VH, DE specifications

Emerson is a well-known brand in the field of automation solutions, offering a range of products that cater to various industries. Among its diverse portfolio, Emerson’s products like DE (Digital Electronics), VH (Variable Frequency Drives), DH (Distributed Control Systems), and VE (Valve Positioners) stand out for their advanced features, cutting-edge technologies, and unique characteristics.

Digital Electronics (DE) from Emerson represents the backbone of modern automation systems. These devices are characterized by their highly reliable digital communication capabilities, providing robust solutions for process monitoring and control. DE products integrate seamlessly with various automation platforms, allowing for easy data exchange and system interoperability. The advanced analytics embedded in these systems enable predictive maintenance strategies, enhancing overall operational efficiency.

Variable Frequency Drives (VH) are integral to motor control technologies, maximizing energy efficiency in various applications. Emerson's VH drives are designed for flexibility, supporting multiple motor types and configurations. These drives utilize pulse width modulation (PWM) technology, allowing for precise speed control and improved application performance. Their built-in protection features help extend motor life, prevent downtime, and reduce maintenance costs. Furthermore, the user-friendly interfaces of VH drives facilitate quick setup and troubleshooting.

Distributed Control Systems (DH) from Emerson provide a holistic approach to managing complex industrial processes. They enable centralized control while ensuring that local operations continue seamlessly. DH systems are characterized by their modular architecture, making them highly scalable and adaptable to changing operational needs. Advanced control algorithms within these systems help optimize processes, ensuring maximum productivity. Additionally, their enhanced cybersecurity features protect critical industrial operations from potential threats.

Emerson's Valve Positioners (VE) play a crucial role in regulating flow and pressure in various processes. These devices provide precise positioning capabilities, enhancing the performance of control valves. The VE systems incorporate smart technologies such as adaptive control and diagnostics, allowing them to self-tune and deliver accurate performance over time. Their compact design and robust build ensure they operate effectively in challenging environments.

In summary, Emerson's DE, VH, DH, and VE offerings embody the latest innovations in automation technology. Their main features, including digital communication, energy efficiency, scalability, and precision control, cater to the diverse demands of modern industries. With these products, Emerson not only enhances operational efficiency but also paves the way for intelligent automation solutions that are crucial for the future of industrial processes.