Emerson VE, VH, DE, DH manual Communications, Calibration

Page 50

Response by Control Type—Advanced Microprocessor Controls

Calibration

Calibration should not be required for most installations. The accuracy of this display is approxi- mately 1%.

The display is calibrated by the slope and intercept values of Analog Input #1. The position of the water is calculated from the analog output of the LT750 using the formula:

position = analog reading/full scale reading X (measured length + slope) + intercept

position is the distance from the LT750 to the position of the detected water.

measured length is the length of the cable which is calculated automatically when the layout is defined. The units for these values are in floor tiles.

The intercept value read from Analog Input #1 is added to the measured position of a water indication to determine which tile to highlight. For example, if water is displayed under the seventh tile but determined to be under the fifth tile, set the offset value to -2 tiles. Use the intercept value to correct errors close to the start of the cable.

Accuracy errors farther out on the cable should be corrected using Analog Input #1's slope value. This value effectively adjusts the measured length of the cable. Increasing the effective length of cable will increase the distance of the water and move the highlighted tile farther along the cable, and vice versa. Unlike the intercept, which adjusts by the same amount for all locations on the cable, the slope increases its effect for larger distances.

The best procedure to calibrate the cable would be to first simulate water close to the LT750, about 5 tiles out. Adjust the intercept to get the correct reading. Next, simulate water 5 tiles from the end. Adjust the slope to get the correct reading.

5.5Communications

The control system uses a two-wire, RS-422 channel to communicate with remote monitoring systems via Liebert Site Products. This communication, directly out of the control, uses a proprietary protocol. Your unit can have a variety of different Site Product devices wired to this port depending on the monitoring system you are using.

Liebert Site Product Device

SiteScan Centralized Monitoring System—Stand alone facility monitoring system

SiteLink BMS Interface Module—For Modbus or BACnet communication to a third party moni- toring system

OpenComms Network Interface Card—For Ethernet connection using SNMP protocol

OpenComms D.O. Interface Card—For discrete outputs of status and alarm conditions

Mini-Remote - Stand alone individual unit remote monitor

ECA2 Communication Adapter—For remote service monitoring directly or via a modem

Consult the User Manual of the appropriate device for specific installation and operation information.

5.5.1Monitor functions:

1.Temperature/Humidity: Present readings

2.Status: Cooling/Heating and Humidifying/Dehumidifying operating status in percent

3.Present Alarms: Alarms presently active

4.Alarm History: 10 most recent alarms (60 most recent alarms for AG)

5.Run Time Log: Operating hours on major components

6.Daily Log: High and Low Temperature & Humidity

42

Image 50 Contents
Liebert Deluxe System/3 Page Table of Contents Main Menu AG-Run Diagnostics Alarm Descriptions and Solutions Temperature ControlSystem Testing Figures Page System Description IntroductionDual Source Cooling Systems Chilled Water SystemsGlycool Chilled Glycol Cooling Systems Initial START-UP Procedure Additional Considerations for Upflow UnitsDisplay the Main Menu-AM Control Advanced Microprocessor Controls SetupBasics Advanced microprocessor AM control menu Alarm History Log Main Menu AM-Status/Alarm DataActive Alarms Operating StatusDefault control and alarm setpoints Main Menu AM-Setpoints/SetupSetup System Selection Analog SensorsFunction Default Range Setup OperationSetup functions and factory default values Select Options Show DIP SwitchesDIP switch settings Calibrate SensorsSetup Alarms Select Control TypeAlarm default time delay Alarm Default Delay secondsHumidity Control Method Standard Alarm MessagesAnalog Setup Calibrate Actuator Run DiagnosticsSet Status Display Show InputsTest Outputs Change PasswordsMain Menu AM-Date and Time Test Control BoardControl Circuit Board Load Control FeaturesMain Menu AM-Status Display Nonvolatile Memory DIP SwitchesCommunications Control OutputsMonitor functions View/Change FunctionsAdvanced Microprocessor with Graphics Control Setup Advanced microprocessor with graphics control panelAdvanced microprocessor with graphics AG control menu Main Menu AG-Status Display Main Menu AG-View/Set AlarmsDisplay the Main Menu-AG Control Default Time Delay Alarm SecondsSetup Water Detect Floor Plan Set Up Custom AlarmsStandard Custom Alarm Messages Installation-LT750 DIP Switch SettingsMain Menu AG-View/Set Control Setpoints Main Menu AG-Setup SystemMain Menu AG-Operating Status Default Settings and Ranges Cold Start DelayAuto Restart Delay IR Flush Overfill infrared humidifiers onlyCalibrate Valve Actuator Select Control AlgorithmMain Menu AG-Run Diagnostics Select Humidity Sensing ModeShow Inputs Main Menu AG-Plot Graphs Dehumidification with Normal or Delayed ReheatMain Menu AG-Date and Time Main Menu AG-Analog/Digital Inputs Read Digital Inputs Set Up Digital InputsMain Menu AG-View Run Hours Log View 24 Hour Run Time HistoryControl Circuit Board On/Off Status Time View Only Silence Alarm Temperature Control Response by Control TYPE-ADVANCED Microprocessor ControlsChilled Water Cooling Glycool CoolingDual Cooling Source Heating Operation Electric ReheatDehumidification/Humidification Required, in Percent % Humidity ControlHot Water/Steam Heat Control Types Proportional ControlHumidification Operation System Activation Dual Cooling Source DehumidificationChilled Water Dehumidification Suggested System Tuning Procedure Intelligent Control Load Control Features Changing factory-set sensor inputs Connecting the Analog SensorsAnalog Sensors Additional connections available after unit deliveryPhysical Connections SetupWater Detection Display Calibration View/Change Functions Change Filter Standard AlarmsAlarm Descriptions and Solutions Compressor OverloadHigh Temperature and Low Temperature Simultaneously Custom Alarms Only With Advanced ControlsHigh Temperature Humidifier Problem Infrared HumidifiersLoss of Air Flow Loss of PowerLow Temperature Low HumidityOptional/Custom Alarms Environmental Control Functions System TestingComponent Operation and MAINTENANCE, Checks and Adjustments Proportional Heating/Cooling/ DehumidificationControl Transformer and Fuses Fan Safety SwitchElectric Panel FirestatFan Impellers and Bearings FiltersBlower Package BeltsCompressor Oil Level Refrigeration SystemElectronic Variable Speed Drive Inverter Suction Superheat Suction PressureDischarge Pressure Thermostatic Expansion Valve OperationAdjustment Hot Gas Bypass Valve OperationOutdoor fan/condenser configuration Air Cooled CondenserGlycol Solution Maintenance Adjustment Johnson Controls/Penn Johnson valvesTesting Function of Valve Water/Glycol Cooled Condensers Shell and Tube CondensersElectrical Failure Compressor ReplacementMechanical Failure Infrared Humidifier Compressor Replacement ProcedureHumidifier Autoflush Operation Autoflush Infrared Humidifier Cleaning SystemChanging Humidifier Lamps Humidifier lampsSteam Generating Humidifier Steam generating humidifierControls Replacing the CanisterPriority Name LED Indication Description Faults-canister generator humidifierHumidifier canister part numbers Capacity Circuit Board AdjustmentsSteam generating humidifier capacity Hz Models Lbs/hr kg/hrVoltage AMP Set Pt Electric ReheatUnit Rated Rated Values Voltage Capacity Chilled water troubleshooting TroubleshootingBlower troubleshooting Symptom Possible Cause Check or RemedyCompressor and refrigeration system troubleshooting Compressor and refrigeration system troubleshooting Dehumidification troubleshooting Glycol pumps troubleshootingHumidifier-steam generator troubleshooting Adjustments onHumidifier-infrared troubleshooting Reheat troubleshootingMaintenance Inspection CHECKLIST-MONTHLY Maintenance Inspection CHECKLIST-SEMIANNUAL Ti n Ne tIti That