Manitowoc Ice QF0400, QF2300, QF0800 Section Installation Instructions Location of Ice Machine

Page 15

Section 2

Installation Instructions

 

 

Location of Ice Machine

The location selected for the ice machine must meet the following criteria. If any of these criteria are not met, select another location.

The location must be free of airborne and other contaminants.

The air temperature must be at least 45°F (7°C), but must not exceed 110°F (43.4°C).

The water temperature must be at least 45°F (7°C), but must not exceed 90°F (32.2°C).

The location must not be near heat-generating equipment or in direct sunlight.

The location must be capable of supporting the weight of the ice machine and a full bin of ice.

The location must allow enough clearance for water, drain and electrical connections in the rear of the ice machine.

The location must not obstruct airflow through or around the ice machine. QF400 airflow is in and out of the front of the ice machine. Refer to below for clearance requirements.

Ice Machine Head Section Clearance Requirements

QF400

Self-Contained

Self-Contained

Air-Cooled

Water-Cooled

 

Top/Sides

5” (12.7 mm)

NA

Back

5” (12.7 mm)

NA

 

 

 

QC700/QF800

Self-Contained

Self-Contained

Air-Cooled

Water-Cooled

 

Top/Sides

8” (20.3 mm)

5” (12.7 mm)

Back

5” (12.7 mm)

5” (12.7 mm)

 

 

 

QF2300

Self-Contained

Remote

Air-Cooled

Air-Cooled

 

Top/Sides

NA

5” (12.7 mm)

Back

NA

5” (12.7 mm)

!Caution

The ice machine head section must be protected if it will be subjected to temperatures below 32°F (0°C). Failure caused by exposure to freezing temperatures is not covered by the warranty. See “Removal from Service/Winterization”.

Ice Machine Heat of Rejection

Series

Heat of Rejection*

Condensing Unit

 

QF400

4000

QC700

7800

QF800

7800

QF2300/RFC2385

21000

*B.T.U. / Hour

Ice machines, like other refrigeration equipment, reject heat through the condenser. It is helpful to know the amount of heat rejected by the ice machine when sizing the air conditioning equipment where self-contained air- cooled ice machines are installed. QF2300 ice machines add an insignificant amount of load to a conditioned space.

Location of Remote Condensing Unit

The location selected for the Remote Condensing Unit must meet the following criteria. If any of these criteria are not met, select another location.

The air temperature must be at least -20°F (-28.9°C) but must not exceed 120°F (49°C).

The location must not allow exhaust fan heat and/or grease to enter the condenser.

The location must not obstruct airflow through or around the condensing unit. Refer to the chart below for clearance requirements.

CONDENSING UNIT CLEARANCE REQUIREMENTS

 

Ice Machine Condensing Unit

Top/Sides

There is no minimum clearance required,

 

although 6” (12.7 cm) is recommended for

 

efficient operation and servicing only.

Front/Back

4’ (1.2 M)

Part Number 000002688

2-5

Image 15
Contents Installation Use and Care Manual Personal Injury Potential Read These Before ProceedingTable of Contents Section Ice Machine Operation Table of ContentsSection Before Calling Service Table of Contents Section Ice Machine Sequence of OperationTable of Contents Remote Condensing Unit How to Read a Model NumberAccessories Model NumbersModel/Serial Number Location Ice Machine Model Number General Information Section Model/Serial Number LocationCommercial Warranty Coverage General Information Section QC700/QF800 AIR Cooled ICE Machine Ice Machine DimensionsQF400 AIR Cooled ICE Machine QC700/QF800 Water Cooled ICE Machine QF2300 Head Section and RFC2385 Remote Condensing Unit B970 Bin Model Dimension a Dimension BInch 56 CM ICE Storage Bins Inch 130 CM ICE Storage Bins Inch 76 CM ICE Storage BinsInch 76 CM Bin Model Dimension a Width Dimension B HeightLocation of Remote Condensing Unit Section Installation Instructions Location of Ice MachineIce Machine Head Section Clearance Requirements Ice Machine Heat of RejectionAir Baffle Condenser Air BaffleLeveling Leg and Foot QC700/QF800 Air-Cooled Ice Machines OnlySection Installation Instructions Electrical Service Installation Instructions Section Electrical Requirements For United Kingdom OnlyIce Machine Head Section QC700C/QF800C ICE Machine Head /1/60 or 208-230/1/60 QC700C/QF800C ICE Machine Head /1/50QF2300 ICE Machine Head /60/1 RFC2385 Remote Condensing Unit 208-230/1/60 Potable Water Inlet Lines Section Installation Instructions Water Supply and DrainsCooling Tower Applications Water-Cooled Models Potable Water SupplyInstallation Instructions Section Typical Water Supply Drain InstallationWater Supply and Drain Line SIZING/CONNECTIONS QF2300/RFC2385 only Usage with NON-MANITOWOC Condensing UnitsFactory Equipment Refrigeration Amounts Route Refrigeration Tubing Line SET LengthLine SET Rise or Drop Roof/Wall PenetrationManitowoc S-Trap Kit Service LoopSupplied service loop is an installation requirement Suction Line OIL TrapsConnecting the line set Connect The Line Set To The Ice Machine Head SectionConnect The Line Set To The Remote Condensing Unit Torque Value’s Open The Valves Prior To Starting The Ice MachineSuction Liquid Min. Insulation Line Open Receiver Service ValveLeak Check The Refrigeration System Insulation RequirementsSuction Shut Off Valve Insulation Typical Remote System Installation Remote AIR-COOLED only Section Installation Instructions Installation ChecklistPotential Personal Injury Situation QF400 Component IdentificationICE Machine Head Section QC700/QF800QF2300 Ice Machine Operation SectionWater Level Check Section Ice Machine Operation Operational ChecksCleaning/Sanitizing Procedure Heavily Scaled Cleaning ProcedureExterior Cleaning Straighten Bent Condenser Fins Cleaning the CondenserAir-Cooled Condenser Self-Contained Air-Cooled FilterModel Amount of Cleaner MANITOWOC’S Cleaning TechnologyPreventative Maintenance Cleaning Procedure QF400 CLEANING/SANITIZING Procedure QC700/QF800/QF2300 Amount of Water Amount of CleanerAmount of Water Amount of Sanitizer CLEANING/SANITIZING Procedure QF400 Only Mix Cleaner and WaterUse Ice machine cleaner CleanerRemoval of Parts for CLEANING/SANITIZING Solution TypeMixed With Water Level Probe Removal Water Level Probe RemovalQF2300 Water Reservoir Cover Removal QC700/QF800 ShownQF2300 Shown Float Valve Removal QC700/QF800 Shown Ice Diverter Removal Water Reservoir RemovalIce Chute Removal Cabinet Removal Bin Door RemovalWater Dump Valve Dump Valve DisassemblyPry Open the Water Regulating Valve Water Cooled Condensing UnitQF400/QC700/QF800 Prior to START-UPFlush Sequence in the ICE Position Ice Machine Sequence of Operation Section QF2300 Problem Possible Cause To Correct ChecklistBefore Calling Service Section Safeguard Feature Reset Procedure Safeguard Indicator LightsStandby Mode Possible Problem List Corrective Action List Analyzing Why SafeGuards May Stop the Ice MachineNo Water Checklist Safeguard ModesBefore Calling Service Section Gear Motor Speed ChecklistGear Motor Speed Temperature Sensor Checklist Temperature is Too High or Low QF400/QC700/QF800This page Intentionally Left Blank Page Manitowoc ICE, INC