Manitowoc Ice QF0800, QF2300, QC0700, QF0400 manual Suction Shut Off Valve Insulation

Page 29

Section 2

Installation Instructions

 

 

Suction Shut Off Valve Insulation

The pre-formed suction shut-off valve insulation is located in the plastic bag taped to the water curtain.

A.Verify valve and schrader caps are tightened to specifications (see Step 6).

PRE-FORMED

INSULATION

TIGHTEN VALVE CAPS

SV3084

TO SPECIFICATIONS

B.Place insulation over schrader valve cap and left side of valve. Position the tab between the mounting bracket and rear panel.

PLACE TAB BETWEEN

VALVE BODY AND PANEL

SV3085

C.Fold insulation and hold against right hand side of valve while securing with electrical tape. Seal the line set insulation to the shut off valve insulation with electrical tape.

FOLD INSULATION OVER

RIGHT SIDE OF VALVE AND

SECURE WITH

ELECTRICAL TAPE

SV3086

Part Number 000002688

2-19

Image 29
Contents Installation Use and Care Manual Personal Injury Potential Read These Before ProceedingTable of Contents Section Ice Machine Operation Table of ContentsSection Before Calling Service Table of Contents Section Ice Machine Sequence of OperationTable of Contents Accessories How to Read a Model NumberModel Numbers Remote Condensing UnitModel/Serial Number Location Ice Machine Model Number General Information Section Model/Serial Number LocationCommercial Warranty Coverage General Information Section QF400 AIR Cooled ICE Machine Ice Machine DimensionsQC700/QF800 Water Cooled ICE Machine QC700/QF800 AIR Cooled ICE MachineQF2300 Head Section and RFC2385 Remote Condensing Unit Inch 56 CM ICE Storage Bins Inch 130 CM ICE Storage Bins Bin Model Dimension a Dimension BInch 76 CM ICE Storage Bins B970Inch 76 CM Bin Model Dimension a Width Dimension B HeightIce Machine Head Section Clearance Requirements Section Installation Instructions Location of Ice MachineIce Machine Heat of Rejection Location of Remote Condensing UnitLeveling Leg and Foot Condenser Air BaffleQC700/QF800 Air-Cooled Ice Machines Only Air BaffleSection Installation Instructions Electrical Service Ice Machine Head Section Installation Instructions Section Electrical RequirementsFor United Kingdom Only QF2300 ICE Machine Head /60/1 QC700C/QF800C ICE Machine Head /1/60 or 208-230/1/60QC700C/QF800C ICE Machine Head /1/50 RFC2385 Remote Condensing Unit 208-230/1/60 Cooling Tower Applications Water-Cooled Models Section Installation Instructions Water Supply and DrainsPotable Water Supply Potable Water Inlet LinesWater Supply and Drain Line SIZING/CONNECTIONS Installation Instructions SectionTypical Water Supply Drain Installation Factory Equipment Refrigeration Amounts QF2300/RFC2385 onlyUsage with NON-MANITOWOC Condensing Units Line SET Rise or Drop Line SET LengthRoof/Wall Penetration Route Refrigeration TubingSupplied service loop is an installation requirement Service LoopSuction Line OIL Traps Manitowoc S-Trap KitConnect The Line Set To The Remote Condensing Unit Connecting the line setConnect The Line Set To The Ice Machine Head Section Torque Value’s Open The Valves Prior To Starting The Ice MachineLeak Check The Refrigeration System Open Receiver Service ValveInsulation Requirements Suction Liquid Min. Insulation LineSuction Shut Off Valve Insulation Typical Remote System Installation Remote AIR-COOLED only Section Installation Instructions Installation ChecklistPotential Personal Injury Situation ICE Machine Head Section Component IdentificationQC700/QF800 QF400QF2300 Ice Machine Operation SectionWater Level Check Section Ice Machine Operation Operational ChecksExterior Cleaning Cleaning/Sanitizing ProcedureHeavily Scaled Cleaning Procedure Air-Cooled Condenser Cleaning the CondenserSelf-Contained Air-Cooled Filter Straighten Bent Condenser FinsModel Amount of Cleaner MANITOWOC’S Cleaning TechnologyPreventative Maintenance Cleaning Procedure QF400 Amount of Water Amount of Sanitizer CLEANING/SANITIZING Procedure QC700/QF800/QF2300Amount of Water Amount of Cleaner CLEANING/SANITIZING Procedure QF400 Use Ice machine cleaner Mix Cleaner and WaterCleaner OnlyMixed With Removal of Parts for CLEANING/SANITIZINGSolution Type QF2300 Water Reservoir Cover Removal Water Level Probe RemovalQC700/QF800 Shown Water Level Probe RemovalQF2300 Shown Float Valve Removal QC700/QF800 Shown Ice Diverter Removal Water Reservoir RemovalIce Chute Removal Cabinet Removal Bin Door RemovalWater Dump Valve Dump Valve DisassemblyPry Open the Water Regulating Valve Water Cooled Condensing UnitFlush Sequence in the ICE Position QF400/QC700/QF800Prior to START-UP Ice Machine Sequence of Operation Section QF2300 Problem Possible Cause To Correct ChecklistStandby Mode Before Calling Service Section Safeguard FeatureReset Procedure Safeguard Indicator Lights No Water Checklist Analyzing Why SafeGuards May Stop the Ice MachineSafeguard Modes Possible Problem List Corrective Action ListGear Motor Speed Before Calling Service SectionGear Motor Speed Checklist Temperature Sensor Checklist Temperature is Too High or Low QF400/QC700/QF800This page Intentionally Left Blank Page Manitowoc ICE, INC