Manitowoc Ice QF0800 Section Installation Instructions Water Supply and Drains, Drain Connections

Page 21

Section 2

Installation Instructions

 

 

Water Supply and Drains

POTABLE WATER SUPPLY

Local water conditions may require treatment of the water to inhibit scale formation, filter sediment, and remove chlorine odor and taste.

Important

If you are installing a Manitowoc water filter system, refer to the Installation Instructions supplied with the filter system for ice making water inlet connections.

POTABLE WATER INLET LINES

Follow these guidelines to install water inlet lines:

Do not connect the ice machine to a hot water supply. Be sure all hot water restrictors installed for other equipment are working. (Check valves on sink faucets, dishwashers, etc.)

If water pressure exceeds the maximum (80 psig 551.5 kPA) recommended pressure, obtain a water pressure regulator from your Manitowoc distributor.

Install a water shut-off valve and union for both the ice making and condenser water lines.

Insulate water inlet lines to prevent condensation.

DRAIN CONNECTIONS

Follow these guidelines when installing drain lines to prevent drain water from flowing back into the ice machine and storage bin:

Drain lines must have a 1.5 inch drop per 5 feet of run (2.5 cm per meter), and must not create traps.

The floor drain must be large enough to accommodate drainage from all drains.

Run separate bin and water-cooled condenser drain lines. Insulate them to prevent condensation.

Vent the bin and ice machine drain to the atmosphere. The ice machine drain requires an 18” vent. Do not vent the condenser drain on water- cooled models.

Drains must have a union or other suitable means to allow in place disconnection from the ice machine when servicing is required.

Cooling Tower Applications

(Water-Cooled Models)

A water cooling tower installation does not require modification of the ice machine. The water regulator valve for the condenser continues to control the refrigeration discharge pressure.

It is necessary to know the amount of heat rejection, and the pressure drop through the condenser and water valves (inlet and outlet) when using a cooling tower on an ice machine.

Water entering the condenser must not exceed 90°F (32.2°C).

Water flow through the condenser must not exceed 5 gallons (19 liters) per minute.

Allow for a pressure drop of 7 psi (48 kPA) between the condenser water inlet and the outlet of the ice machine.

Water exiting the condenser must no exceed 110°F (43.3°C).

Important

The Commonwealth of Massachusetts requires that all water-cooled models must be connected only to a closed loop, cooling tower system.

Part Number 000002688

2-11

Image 21
Contents Installation Use and Care Manual Personal Injury Potential Read These Before ProceedingTable of Contents Section Ice Machine Operation Table of ContentsSection Before Calling Service Table of Contents Section Ice Machine Sequence of OperationTable of Contents Accessories How to Read a Model NumberModel Numbers Remote Condensing UnitModel/Serial Number Location Ice Machine Model Number General Information Section Model/Serial Number LocationCommercial Warranty Coverage General Information Section QF400 AIR Cooled ICE Machine Ice Machine DimensionsQC700/QF800 Water Cooled ICE Machine QC700/QF800 AIR Cooled ICE MachineQF2300 Head Section and RFC2385 Remote Condensing Unit Inch 56 CM ICE Storage Bins Inch 130 CM ICE Storage Bins Bin Model Dimension a Dimension BInch 76 CM ICE Storage Bins B970Inch 76 CM Bin Model Dimension a Width Dimension B HeightIce Machine Head Section Clearance Requirements Section Installation Instructions Location of Ice MachineIce Machine Heat of Rejection Location of Remote Condensing UnitLeveling Leg and Foot Condenser Air BaffleQC700/QF800 Air-Cooled Ice Machines Only Air BaffleSection Installation Instructions Electrical Service Installation Instructions Section Electrical Requirements For United Kingdom OnlyIce Machine Head Section QC700C/QF800C ICE Machine Head /1/60 or 208-230/1/60 QC700C/QF800C ICE Machine Head /1/50QF2300 ICE Machine Head /60/1 RFC2385 Remote Condensing Unit 208-230/1/60 Cooling Tower Applications Water-Cooled Models Section Installation Instructions Water Supply and DrainsPotable Water Supply Potable Water Inlet LinesInstallation Instructions Section Typical Water Supply Drain InstallationWater Supply and Drain Line SIZING/CONNECTIONS QF2300/RFC2385 only Usage with NON-MANITOWOC Condensing UnitsFactory Equipment Refrigeration Amounts Line SET Rise or Drop Line SET LengthRoof/Wall Penetration Route Refrigeration TubingSupplied service loop is an installation requirement Service LoopSuction Line OIL Traps Manitowoc S-Trap KitConnecting the line set Connect The Line Set To The Ice Machine Head SectionConnect The Line Set To The Remote Condensing Unit Torque Value’s Open The Valves Prior To Starting The Ice MachineLeak Check The Refrigeration System Open Receiver Service ValveInsulation Requirements Suction Liquid Min. Insulation LineSuction Shut Off Valve Insulation Typical Remote System Installation Remote AIR-COOLED only Section Installation Instructions Installation ChecklistPotential Personal Injury Situation ICE Machine Head Section Component IdentificationQC700/QF800 QF400QF2300 Ice Machine Operation SectionWater Level Check Section Ice Machine Operation Operational ChecksCleaning/Sanitizing Procedure Heavily Scaled Cleaning ProcedureExterior Cleaning Air-Cooled Condenser Cleaning the CondenserSelf-Contained Air-Cooled Filter Straighten Bent Condenser FinsModel Amount of Cleaner MANITOWOC’S Cleaning TechnologyPreventative Maintenance Cleaning Procedure QF400 CLEANING/SANITIZING Procedure QC700/QF800/QF2300 Amount of Water Amount of CleanerAmount of Water Amount of Sanitizer CLEANING/SANITIZING Procedure QF400 Use Ice machine cleaner Mix Cleaner and WaterCleaner OnlyRemoval of Parts for CLEANING/SANITIZING Solution TypeMixed With QF2300 Water Reservoir Cover Removal Water Level Probe RemovalQC700/QF800 Shown Water Level Probe RemovalQF2300 Shown Float Valve Removal QC700/QF800 Shown Ice Diverter Removal Water Reservoir RemovalIce Chute Removal Cabinet Removal Bin Door RemovalWater Dump Valve Dump Valve DisassemblyPry Open the Water Regulating Valve Water Cooled Condensing UnitQF400/QC700/QF800 Prior to START-UPFlush Sequence in the ICE Position Ice Machine Sequence of Operation Section QF2300 Problem Possible Cause To Correct ChecklistBefore Calling Service Section Safeguard Feature Reset Procedure Safeguard Indicator LightsStandby Mode No Water Checklist Analyzing Why SafeGuards May Stop the Ice MachineSafeguard Modes Possible Problem List Corrective Action ListBefore Calling Service Section Gear Motor Speed ChecklistGear Motor Speed Temperature Sensor Checklist Temperature is Too High or Low QF400/QC700/QF800This page Intentionally Left Blank Page Manitowoc ICE, INC
Related manuals
Manual 150 pages 297 b