Cornelius R-404A REFRIGERANT Control Panel Switches, Cannot be Deactivated, Messages not

Page 71

Trouble

Probable Cause

Remedy

ALL CONTROL PANEL

E. Flat cable connected between

E. Check cable for pinched or

SWITCHES NOT OPERATING.

control switch module and

broken wire condition and repair

(cont’d)

master circuit board pinched

or replace as necessary.

 

and shorted out or broken wire

 

 

in cable.

 

F.Master circuit board not operating properly.

F.Replace master circuit board.

CONTROL PANEL SWITCHES

A.

Not pressing and holding

A. Press and hold ‘‘SECURITY

CANNOT BE DEACTIVATED.

 

‘‘SECURITY SWITCH’’ for 3

SWITCH’’ for 3 seconds to

 

 

seconds to deactivate control

deactivate control switches.

 

 

switches.

 

 

B.

‘‘SECURITY SWITCH’’

B. Replace control panel switch

 

 

inoperable.

module.

 

 

 

 

PARTIAL MESSAGE OR DULL

A.

Extremely low voltage.

A. Upgrade voltage.

(POORLY ILLUMINATED)

 

 

 

DISPLAY.

 

 

 

 

 

 

 

ONE OR MORE FAULT

A. Flat cable not properly

MESSAGES NOT

connected to fault message

OPERATING.

module or master circuit

 

board.

 

B. Flat cable connected between

 

fault message module and

 

master circuit board pinched

 

and shorted out or broken wire

 

in cable.

A.Properly connect flat cable to fault message module or master circuit board.

B.Check cable for pinched or broken wire condition and repair or replace as necessary.

C.External sensing device failing to signal master circuit board which in turn signals fault message display.

C.Replace or repair external sensing device.

D. External sensing devices cable D.

Make sure external sensing

connectors not securely

devices cable connectors are

connected to master circuit

securely connected to master

board connectors.

circuit board connectors.

E.Disconnected or broken wire between master circuit board connector and external sensing device.

E.Connect or repair wire between master circuit board connector and external sensing device.

F.

Master circuit board not

F.

Replace master circuit board.

 

operating properly.

 

 

G.

Fault message display

G.

Replace fault message display

 

module not operating properly.

 

module.

 

 

 

 

ALL FAULT MESSAGES NOT A.

No electrical power to Unit.

A.

Connect electrical power to Unit.

OPERATING.

 

 

 

B.Flat cable not properly connected to fault message module or master circuit board.

B.Properly connect flat cable to fault message module or master circuit board.

C.Flat cable connected between fault message module and master circuit board pinched and shorted out or broken wire in cable.

C.Check cable for pinched or broken wire condition and repair or replace as necessary.

312028000

64

Image 71
Contents To the Installer Table of Contents Table of Contents cont’d Preparing Unit for SHIPPING, STORING, or Relocating Programming Main Menu Selections Onto Message DisplayVIS Read Actual Viscosity Readout of Product Water Strainer Screen and Double Liquid Check Valve‘‘ERROR 1’’ or ‘‘ERROR 2’’ Fault Message Goes on During Product Carbonation AdjustmentDaily Cleaning of Unit Sanitizing Syrup Systems Troubleshooting Control Panel Switches and FaultList of Figures Defrost Cycle does not Cancel After Pressing ‘‘CANCELFreeze Cylinder Automatic Defrost Cycle does not Table of Contents cont’d Unit Description General DescriptionGeneric Flavor Tabs AccessoriesService Tools Theory of OperationAutomatic Defrost System Defrost SystemsManual Defrost System ‘‘WAKE UP’’ Wake UP Time ‘‘SLEEP’’ Sleep TimeFlow Diagram This page Left Blank Intentionally Identification of LOOSE-SHIPPED Parts Unpacking and InspectionHZ Unit Electrical Power RequirementsSelecting Location Installing Drip Tray Drain Hose KIT Item Installing UnitInstalling Leveling Legs Installing Drip Tray Supports Item 7 and ItemConnecting CO2 Source Line to Unit CO2 Inlet Line Installing Primary CO2 Regulator Assembly on CO2 CylinderElectrical BOX Connecting City Plain Water Source Line to UnitConnecting Electrical Power Circuit to the Unit Adjusting Carbonator Secondary CO2 Regulator Turning on Electrical Power to UnitAdjusting Primary CO2 Regulator Adjusting Product Blender Tanks Secondary CO2Control Panel ASS’Y Hidden Security Switch Message DisplayChecking Unit for SYRUP, CO2, or Plain Water Leaks Filling Freeze Cylinders with ProductPlacing Unit in Operating Location Adjusting Beater Motor Current Either SideProgramming Main Menu Selection Onto Message Display Setting Clock Time of DAYMain Menu Selections Programming ‘‘DEFROST’’ Automatic Settings Into UnitMenu Selections Programming ‘‘SLEEP’’ Sleep Time Into Unit Switch FunctionDIP Switch Functions Programming Point of Sale Message Display Programming ‘‘WAKE UP’’ Wake UP Time Into UnitAdjusting VIS SET Product Viscosity of Dispensed Product Master and Relay Circuit Board ‘‘VOLTAGE’’ Displayed Voltage Readout 312028000 Gallons = a X Syrup Minutes Totals Menu Commands DescriptionSyrup Minutes Side BrixProgramming Proper Refrigerant Type Into Unit Electronics Displayed Error ConditionsDisplayed Error Conditions Control Panel ASS’Y Switches Control Panel ASS’Y Switches and Displayed Messages‘‘SECURITY SWITCH.’’ Control Panel Assembly Display MessagesFreeze Cylinders Manual or Automatic Defrost Systems Product Shutoff Valves ‘‘SLEEP’’ Sleep Time OperationFaceplate Relief Valves Product Sample Valves‘‘OVERRUN’’, AS Applied to Frozen Carbonated Beverages Syrup Flow RegulatorsDispensing Valves Dispensed Product ConditionsReplenishing Syrup Supply Operating CharacteristicsOperating Unit Checking CO2 Supply Cleaning and SanitizingCleaning Condenser Coil Product Flavor ChangeAdjustments Adjusting ‘‘VIS SET’’ Product Viscosity of Dispensed Product Cleaning CO2 GAS Check Valves Back Panel Preparing Unit for SHIPPING, STORING, or RelocatingPeriodic Inspection TOP PanelClosing Front Access Door Opening and Closing Front Access DoorFront Access Panel Opening Front Access DoorOperating Controls Unit Internal Components SELF-CLOSING Dispensing Valve 312028000 Adjusting Carbonated Water Flow Rate Adjusting Plain Water Pressure RegulatorFreeze Cylinder Cutaway View Servicing Beater Motor Drive SHAFT/SEAL Assembly Beaters and Scraper Blades Installation Adjusting CO2 Regulators Adjusting Brix WATER-TO-SYRUP ‘‘RATIO’’ of Dispensed Product Sanitizing Syrup Systems Product Carbonation AdjustmentDaily Cleaning of Unit To disconnect soft drink tank from Unit syrup system 312028000 Servicing Carbonator Water Pump Water Strainer Screen Yearly or After Water System DisruptionServicing Carbonator Water Pump Double Liquid Check Valve Liquid Check Valve AssemblyReplenishing Syrup Supply Syrup Flavor Change Service and Maintenance SectionReplenishing CO2 Supply Water Strainer Screen and Double Liquid Check Valve Replacing Freeze Cylinder Beater Drive Motor ServicedMents in Small Increments Adjusting Carbonator Tank Liquid LevelCarbonator Liquid Level Control Switch Adjustment Refrigeration Flow Diagram Wiring Diagram This page Left Blank Intentionally Troubleshooting Control Panel Switches and Fault Messages Cannot be Deactivated Control Panel SwitchesPoorly Illuminated Display ONE or More Fault ALL Fault Messages not aFault Message Goes on ALL Fault Message not‘‘CO2 OUT’’ Fault Message ‘‘H2O OUT’’ Fault MessageTroubleshooting Product Blender Tanks and Carbonator Troubleshooting Dispensed Product FREEZE-UP Frozen ProductConsistency Varies ExcessivelyUnit Part Numbers Illustrated Parts BreakdownOvercounter FCB POST-MIX Dispenser FCB POST-MIX Dispenser FCB POST-MIX Dispenser cont’d Name Secondary CO2 Regulator Components Secondary CO2 Regulator ASS’Y CO2 Regulator Assembly Blender and Tubing Components Tubing Assembly Carb Water Tubing Assembly Water Solenoid to Blender Solenoid Valve Assembly Blender Components Control BOX and Display Panel Components Faceplate Assembly Dispensing Valve Assembly Carbonator Components Carbonator Tank and Linkage Assembly Pump and Motor ASS’Y Beater Motor Drive SHAFT/SEAL ASS’Y Warranty This page Left Blank Intentionally One Cornelius Place Anoka, Minnesota 612 800