DCA-600SSV — GEN. START-UP PROCEDURE (MANUAL)
BEFORE STARTING
CAUTION - LETHAL EXHAUST HAZARD
The engine's exhaust contains harmful emissions.
ALWAYS have adequate ventilation when operating. Direct exhaust away from nearby personnel.
If applicable perform the following:
■Apply commercial power to the internal battery charger receptacle (to ensure good starting) via commercial power. An external power cord will be required.This capability is an option.
■Apply commercial power to the jacket water heater receptacle (not necessary for warm climates) via commercial power.An external power cord will be required.This capability is an option.
Generator and Control Panel
WARNING - STARTINGTHE GENERATOR
NEVER! manually start the engine with the main, GFCI or auxiliary circuit breakers in the ON (closed) position.
1. Press the main circuit breaker “OFF” switch (Figure 40).
Figure 40. Main Circuit Breaker OFF Switch
2.Verifythatthemain circuit breaker “OFF” lamp (Figure 41) is lit (ON).
3.Place the G.F.C.I. andaux.circuitbreakers(Figure42) in the “OFF” position prior to starting the engine.
Figure 42. GFCI and Auxiliary
Circuit Breakers (OFF)
4.Connect the load to the UVWO terminals or auxiliary receptacles as shown in Figure 43. These load connection points can be found on the output terminal panel. To gain access to the UVWO terminals or other power receptacles, unlock the access cover and lift the door.
5.Tighten the UVWO terminal nuts securely to prevent load wires from slipping out.
Figure 43. Load Connections
6. Close all engine enclosure doors (Figure 44).
Figure 41. Main Circuit Breaker OFF Lamp | CORRECT | INCORRECT |
|