Multiquip operation manual DCA-600SSV- Load Application, Single Phase Load, Three Phase Load

Page 29

DCA-600SSV— LOAD APPLICATION

Single Phase Load

Always be sure to check the nameplate on the generator and equipment to insure the wattage, amperage and frequency requirements are satisfactorily supplied by the generator for operating the equipment.

Generally, the wattage listed on the nameplate of the equipment is its rated output. Equipment may require 130— 150% more wattage than the rating on the nameplate, as the wattage is influenced by the efficiency, power factor and starting system of the equipment.

If wattage is not given on the equipment's

NOTE name plate, approximate wattage may be determined by multiplying nameplate voltage by the nameplate amperage.

WATTS = VOLTAGE x AMPERAGE

The power factor of this generator is 0.8. See Table 5 below when connecting loads.

 

 

Table 5. Power Factor By Load

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Type Of Load

 

 

 

 

 

Power Factor

 

 

 

 

 

 

 

 

 

 

 

Single-phase induction motors

 

 

0.4 - 0.75

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Electric heaters, incandescent

 

 

 

 

1.0

 

 

 

 

lamps

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fluorescent lamps, mercury lamps

 

 

0.4 - 0.9

 

 

 

 

 

 

 

 

 

 

 

 

 

Electronic devices, communication

 

 

1.0

 

 

 

 

equipment

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Common power tools

 

 

 

 

 

 

0.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 6. Cable Selection (60 Hz, Single Phase Operation)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Current in

Load In Watts

 

 

 

Maximum Allowable Cable Length

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Amperes

At 120

At 240

 

#10 Wire

 

#12 Wire

 

#14 Wire

 

#16 Wire

 

 

Volts

Volts

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.5

300

600

 

1000 ft.

 

600

ft.

 

375 ft.

 

250 ft.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

600

1200

 

500

ft.

 

300

ft.

 

200 ft.

 

125 ft.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7.5

900

1800

 

350

ft.

 

200

ft.

 

125 ft.

 

100 ft.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

1200

2400

 

250

ft.

 

150

ft.

 

100 ft.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

15

1800

3600

 

150

ft.

 

100

ft.

 

65 ft.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20

2400

4800

 

125

ft.

 

75 ft.

 

50 ft.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CAUTION: Equipment damage can result from low voltage.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Three Phase Load

When calculating the power requirements for 3-phase power use the following equation:

Motors and motor-driven

NOTEequipment draw much greater current for starting than during operation.

An inadequate size connecting cable which cannot carry the required load can cause a voltage drop which can burn out the appliance or tool and overheat the cable. See Table 5.

When connecting a resistance load such as an incandescent lamp or electric heater, a capacity of up to the generating set’s rated output (kW) can be used.

When connecting a fluorescent or mercury lamp, a capacity of up to the generating set’s rated output (kW) multiplied by 0.6 can be used.

When connecting an electric drill or other power tools, pay close attention to the required starting current capacity.

When connecting ordinary power tools, a capacity of up to the generating set’s rated output (kW) multiplied by 0.8 can be used.

DANGER - ELECTRICAL SYSTEM HAZARDS

Before connecting this generator to any building’s electrical system, a licensed electrician must install an isolation (transfer) switch. Serious damage to the building’s electrical system may occur without this transfer switch.

If 3Ø load (kVA) is not given on the equipment nameplate,

NOTEapproximate 3Ø load output maybedeterminedbymultiplying voltage by amperage by 1.732.

DCA-600SSV — OPERATION AND PARTS MANUAL — REV. #0 (07/13/09) — PAGE 29

Image 29
Contents Model DCA-600SSV Proposition 65WARNING Administrator Reporting Safety DefectsTable of Contents Ordering parts has never been easier Parts Ordering ProceduresDCA-600SSV Specifications Dimensions DCA-600SSV Dimensions TOP, Side and FrontHazard Symbols DCA-600SSV Safety Message Alert SymbolsThis generator, other property DCA-600SSV Safety Message Alert SymbolsBurns General SafetyGenerator Grounding Electrical SafetyDCA-600SSV Rules for Safe Operation Battery Safety Maintenance SafetyEmergencies Towing & Transporting SafetyDCA-600SSV Rules for Safe Operation DCA-600SSV Generator Decals Machine Safety DecalsDCA-600SSV Generator Decals 16 DCA-600SSV Operation and Parts Manual REV. #0 07/13/09 DCA-600SSV Generator Decals Typical Generator Grounding Application DCA-600SSV InstallationMounting Outdoor InstallationDCA-600SSV General Information Generator Major Components DCA-600SSV Major ComponentsPilot Lamp Indicates that the generator is working properly DCA-600SSV Generator Control PanelDCA-600SSV Generator Control Panel When the circuitLamp will be turned OFF Be turned onDCA-600SSV Engine Operating Panel Will stop the engine automatically DCA-600SSV Engine Operating PanelOutput Terminal Familiarization DCA-600SSV Outputterminal Familiarization120VAC Gfci Receptacles DCA-600SSV Output Terminal Panel FamiliarizationMaximum Power Output KW Connecting LoadsDCA-600SSV Output Terminal Panel Familiarization Over Current RelayDCA-600SSV- Load Application Single Phase LoadThree Phase Load Voltage Change-Over Board Generator OutputVoltagesMaximum Amps Rated Maximum AmpsACVoltmeter Gauge Reading DCA-600SSV Generator OUTPUTS/GAUGE ReadingAC Ammeter Gauge Reading Uvwo Terminal Output Voltages DCA-600SSV Output Terminal Panel Connections3Ø-240V Uvwo Terminal Output Voltages 1Ø-240V Uvwo Terminal Output Voltages3Ø-480V Uvwo Terminal Output Voltages DCA-600SSV Output Terminal Panel Connections1Ø-480V Uvwo Terminal Output Voltages 1Ø-277V Uvwo Terminal Output VoltagesLubrication Oil DCA-600SSV SetupCircuit Breakers Fuel from the secondary inner Refueling ProcedureRefueling 36 DCA-600SSV Operation and Parts Manual REV. #0 07/13/09 Cleaning the Radiator DCA-600SSV- SetupAir Cleaner Fan Belt Tension Operation Freezing WeatherBattery Cable Installation BatteryWiring AlternatorGenerator and Control Panel DCA-600SSV GEN. START-UP Procedure ManualPlace the engine speed switch in the LOW position Figure DCA-600SSV- Generator START-UP Procedure ManualVerify that the main circuit breaker on lamp is lit on DCA-600SSV- Generator START-UP Procedure ManualSet the engine speed switch to the High position DCA-600SSV Generator START-UP Procedure Auto ModeEmergency Shutdown Procedure DCA-600SSV Generator SHUT-DOWN ProcedureNormal Shutdown Procedure Air Cleaner DCA-600SSV MaintenanceAir Cleaner with Dust Indicator General InspectionCleaning Inside the Fuel Tank Service DailyCleaning the Fuel Strainer Fuel AdditionAir Removal Radiator CleaningCheck Oil Level Replacing Oil FilterTo ensure adequate starting Battery Charger & Jacket Water Heater Power ConnectionsDCA-600SSV -TRAILER Brakes Maintenance Tires/Wheels/Lug Nuts DCA-600SSV -TRAILER MaintenanceTire Wear/Inflation SuspensionLug nuts Lug Nut Torque RequirementsStart all wheel lug nuts by hand Trailer Wiring Diagram 5-Pin DCA-600SSV -TRAILER-WIRING DiagramDCA-600SSV -TRAILER-WIRING Diagram Generator Wiring Diagram DCA-600SSV -GENERATORWIRING DiagramMain Circuit Breaker Wiring Diagram DCA-600SSV Generator Wiring Diagram Main BreakerDCA-600SSV Enginewiring Diagram DCA-600SSV -TROUBLESHOOTING Engine Smooth DCA-600SSV -TROUBLESHOOTING EngineGenerator Troubleshooting DCA-600SSV -TROUBLESHOOTING GeneratorEngine Controller Troubleshooting Mpec DCA-600SSV -TROUBLESHOOTING Engine ControllerExample Error Code DCA-600SSV-TROUBLESHOOTING Diagnostic LampMethod of Operation For a complete understandingDCA-600SSV Operation and Parts Manual REV. #0 07/13/09 DCA-600SSV- Explanation of Code in Remarks Column Sample Parts ListQty Description DCA-600SSV Suggested Spare PartsDCA-600SSV w/SA6D170AE-1VOLVO Engine DCA-600SSV Generator Assy 8171020004 06018423668171020504 8461070002DCA-600SSV Generator ASSY. 8461312004 74313100030016308095 11A 0040008000DCA-600SSV Control BOX Assy 0601806153 C42140016020017108020 C4261506003DCA-600SSV Control BOX ASSY. 7431861113 39-C 00412140007431852104 001710803572 DCA-600SSV Operation and Parts Manual REV. #0 07/13/09 8481814503 0605010502C4214300904 0601850349DCA-600SSV Engine and Radiator Assy 0602015240 C49242002840602015241 0602046623DCA-600SSV Engine and Radiator ASSY. 0019206025 01500000180130404000 0130204000DCA-600SSV Engine Operating Panel Assy 0017112030 C4484002102C4352102203 8085182004DCA-600SSV Outputterminal Assy 7521860504 C42317006037521850504 0010112040DCA-600SSV Outputterminal ASSY. 32-1 0221200150 C32616007040017106030 0601812598DCA-600SSV Battery Assy C9109100704 01687190520805007804 0805006504DCA-600SSV Muffler Assy 0019210020 C4331100802C4334200904 0019210030DCA-600SSV Fueltank Assy 0845500104 C43640022030810105400 0264100505DCA-600SSV Enclosure #1 Assy 3875116304 C4414003302C4414100204 C4414100304DCA-600SSV Enclosure #1 ASSY. 35B 0040020000 35A 003002000035C 0041220000 C4434200103DCA-600SSV Enclosure #2 Assy 3875151004 C44440013030207106000 C4444000103DCA-600SSV Enclosure #2 ASSY. 42A C4494501604 C4464202403C4464202503 43A C4494501604DCA-600SSV Enclosure #3 Assy 0019110070 C44542060030042310000 0042410000DCA-600SSV Rubber Seal Assy 0228901440 02292016500228901670 0228901020DCA-600SSV Nameplate and Decals 0800520904 08005201000800520814 0800564004104 DCA-600SSV Operation and Parts Manual REV. #0 07/13/09 6360620004 13206209040840607104 0800615102Freightpolicy Terms and Conditions of Sale PartsDCA-600SSV Operation and Parts Manual REV. #0 07/13/09 Heres HOW to GET Help