DCA-70SSJU SERIES — GENERATOR OUTPUTS
Generator OutputVoltages
A wide range of voltages are available to supply voltage for many different applications. Voltages are selected by using the voltage selector switch (Figure 15). To obtain some of the voltages as listed in Table 6 (see below) will require a fine adjustment using the voltage regulator (VR) control knob located on the control panel.
Voltage Selector Switch
The voltage selector switch (Figure 15) is located above the UVWO Hard Wire
Generator Amperage
Tables 7 and 8 describe the generator’s current output capa- bility for both
Table 7. Generator Ampere
Ratings — 1Ø
kW | 240V | 120V |
|
|
|
20 | 83 | 166 |
|
|
|
25 | 104 | 208 |
30 | 225 | 250 |
|
|
|
35 | 145 | 291 |
|
|
|
40 | 166 | 333 |
|
|
|
45 | 187 | 375 |
|
|
|
50 | 208 | 417 |
60 (Max) | 250 | 500 |
|
|
|
Figure 15. Voltage Selector Switch
Voltage Selector Switch Locking Button
The voltage selector switch has a locking button to protect the generator and load from being switched while the engine is running. To lock the voltage selector switch, press and hold the red button located at the bottom of the switch.
Table 8. Generator Ampere Ratings — 3Ø
kW | 208V | 240V | 480V |
|
|
|
|
20 | 59 | 60 | 30 |
|
|
|
|
25 | 87 | 75 | 38 |
30 | 104 | 90 | 45 |
|
|
|
|
35 | 121 | 105 | 53 |
|
|
|
|
40 | 139 | 120 | 60 |
|
|
|
|
45 | 156 | 136 | 68 |
|
|
|
|
50 | 174 | 152 | 76 |
60 | 208 | 181 | 99 |
|
|
|
|
CAUTION:
NEVER change the position of the voltage selector switch while the engine is running. ALWAYS place circuit breaker in the open position before selecting voltage.
Table 6. Voltages Available
Three Phase | 208 VOLT | 220 VOLT | 240 VOLT | 416 VOLT | 440 VOLT | 480 VOLT | |
(Switchable) | |||||||
|
|
|
|
|
| ||
Single Phase | 120 VOLT | 127 VOLT | 139 VOLT | 240 VOLT | 254 VOLT | 277 VOLT | |
(Switchable) | |||||||
|
|
|
|
|
|
PAGE 32 —