DCA-70SSJU SERIES — GENERATOR START-UP PROCEDURE (MANUAL)
WARNING:
The engine's exhaust contains harmful emissions. ALWAYS have adequate ventilation when operating. Direct exhaust away from nearby personnel.
23.Set engine speed switch to “LOW ” (Figure 65).
Figure 65. Engine Speed Switch (Low)
Before Starting
Engine Operating Panel S/N 73002141~
CAUTION:
NEVER! manually start the engine with the main, GFCI or auailliary circuit breakers in the ON (closed) position.
Steps 20 thru 31 are referenced for Engine Operating Panel S/N 73002141~ (Figure 63).This unit does not have a key ignition switch or a throttle lever. It does have an “engine speed switch” that is used in conjunction with the MPEC unit.
Figure 63. Engine Operating Panel
S/N 73002141~
24.Place the
Figure 66. Auto-Off/Reset-Manual Switch
25.Once the engine is warm and the engineisrunningproperly, set the engine speed switch to “HIGH ” (Figure 67).
Figure 67. Engine Speed Switch (High)
26.Verify that the "Engine Running" status LED on the MPEC unit (Figure 68) is "ON" (lit) after the engine has been started.
20.Perform steps 1 through 4 in the Before Starting section (page
21.In cold weather conditions, perform step 6 in the Before Starting section (page 42) as outlined in the Manual Generator
22.Place the voltage selector switch in the desired voltage position (Figure 64).
Figure 64. Voltage Selector
Switch
Figure 68. Engine Running LED (ON)
27.Continue operating the generator as outlined in steps 11 thru 19 (pages
PAGE 44 —