DCA-70SSJU SERIES — GENERATOR START-UP PROCEDURE (AUTO MODE)
DANGER: Before connecting this generator to any building’s electrical system, a licensed electrician must install an isolation (transfer)
switch. Serious injury or death may result without this transfer switch.
CAUTION:
When connecting the generator to a isolation (transfer) switch, ALWAYS have power applied to the generator's internal battery charger. This will ensure that the engine will not fail due to a dead battery.
When the generator is set in the “AUTO” mode, the generator will automically start in the event of
NOTE comercial power falling below a prescribed level by means of a contact closure that is generated automatically by a transfer switch.
CAUTION:
The Engine Speed Switch must be set to the “HIGH” position when running in the
30.Place the Off/Manual/Auto switch (Figure 70) in the “AUTO“ position .
Figure 70. Off/Manual Auto Switch (AUTO)
31.Continue to follow the steps outlined in the “Manual
WARNING:
When running the generator in the “AUTO“ mode, remember the generator can start up at any time without warning. NEVER attempt to perform any maintenance when the generator is in the auto mode.
28.Perform steps 20 through 22 in the Before Starting section (pages 44) as outlined in the Manual Starting Procedure.
29.Set the engine speed switch (Figure 69) to the “HIGH” position.