Multiquip DCA125USI3CAN manual Load Application, Single Phase Load, Three Phase Load, Type of Load

Page 25

Load Application

Single Phase Load

Always be sure to check the nameplate on the generator and equipment to insure the wattage, amperage, frequency, and voltage requirements are satisfactorily supplied by the generator for operating the equipment.

Generally, the wattage listed on the nameplate of the equipment is its rated output. Equipment may require 130—150% more wattage than the rating on the nameplate, as the wattage is influenced by the efficiency, power factor and starting system of the equipment.

NOTICE

If wattage is not given on the equipment’s name plate, approximate wattage may be determined by multiplying nameplate voltage by the nameplate amperage.

WATTS = VOLTAGE x AMPERAGE

The power factor of this generator is 0.8. See Table 5 below when connecting loads.

Table 5. Power Factor By Load

 

Type of Load

 

 

Power Factor

Single-phase induction motors

 

 

0.4-0.75

 

 

 

 

Electric heaters, incandescent lamps

 

1.0

 

Fluorescent lamps, mercury lamps

 

0.4-0.9

Electronic devices, communication

 

1.0

 

equipment

 

 

 

 

 

 

 

 

 

 

 

 

Common power tools

 

 

 

0.8

 

 

 

 

 

 

 

 

 

 

Table 6. Cable Selection (60 Hz, Single Phase Operation)

 

 

 

 

 

 

 

 

Current

Load in Watts

Maximum Allowable Cable Length

 

 

 

 

 

 

 

 

in

At 100

At 200

#10 Wire

#12 Wire

#14 Wire

 

#16 Wire

Amperes

 

Volts

Volts

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.5

300

600

1000 ft.

600 ft.

375 ft.

 

250 ft.

 

 

 

 

 

 

 

 

 

5

600

1200

500 ft.

300 ft.

200 ft.

 

125 ft.

 

 

 

 

 

 

 

 

 

7.5

900

1800

350 ft.

200 ft.

125 ft.

 

100 ft.

 

 

 

 

 

 

 

 

 

10

1200

2400

250 ft.

150 ft.

100 ft.

 

 

 

 

 

 

 

 

 

 

 

15

1800

3600

150 ft.

100 ft.

65 ft.

 

 

 

 

 

 

 

 

 

 

 

20

2400

4800

125 ft.

75 ft.

50 ft.

 

 

 

 

 

 

 

 

 

 

 

 

CAUTION: Equipment damage can result from low voltage

 

 

 

 

 

 

 

 

 

 

Three Phase Load

When calculating the power requirements for 3-phase power use the following equation:

NOTICE

If 3Ø load (kVA) is not given on the equipment nameplate, approximate 3Ø load may be determined by multiplying voltage by amperage by 1.732.

NOTICE

Motors and motor-driven equipment draw much greater current for starting than during operation.

An inadequate size connecting cable which cannot carry the required load can cause a voltage drop which can burn out the appliance or tool and overheat the cable. See Table 6.

„„When connecting a resistance load such as an incandescent lamp or electric heater, a capacity of up to the generating set’s rated output (kW) can be used.

„„When connecting a fluorescent or mercury lamp, a capacity of up to the generating set’s rated output (kW) multiplied by 0.6 can be used.

„„When connecting an electric drill or other power tools, pay close attention to the required starting current capacity.

When connecting ordinary power tools, a capacity of up to the generating set’s rated output (kW) multiplied by 0.8 can be used.

DANGER

Before connecting this generator to any building’s electrical system, a licensed electrician must install an isolation (transfer) switch. Serious damage to the building’s electrical system may occur without this transfer switch.

DCA125USI3CAN 60 hz Generator • operation and parts manual — rev. #2 (09/24/13) — page 25

Image 25
Contents Model DCA125USI3CAN Parts List NO. M3874400004Fuel and chemical warnings Administrator Reporting Safety DefectsNhtsa DCA125USI3CAN Generator Table of ContentsChoose from three easy options SaFetY meSSageS Safety InformationSaFetY SYmBolS Generator Safety GeNeral SaFetYRestricted. If the air fl ow is ENGiNE SafetyIf operating in speed ranges above the maximum allowable TOWiNG Safety FUel SaFetY„ Never use fuel as a cleaning agent From fuel vapors or if fuel is spilled on a hot engineGrounding Safety EleCtrICal SaFetYPower Cord/Cable Safety DeathENvIroNmeNtal SaFetY BatterY SaFetYModel Isuzu 4HK1XYGD-03 Tier SpecificationsDimensions DimensionsTypical Generator Grounding Application InstallationIndoor Installation Outdoor InstallationMounting Generator GroundingGeneral Information Major Components Generator Control Panel Generator Control PanelPage Engine Operating Panel Module Fuel Gauge Indicates amount of diesel fuel availableTerminal legs O and Ground are considered bonded grounds Output Terminal FamiliarizationOutput Terminal Panel is provided with the following VAC Gfci Receptacles Removing the Plastic Face Plate Hard Wire Hookup PanelTwist Lock Dual Voltage 120/240 VAC Receptacles Over Current Relay Connecting LoadsThree Phase Load Single Phase LoadLoad Application Type of LoadVoltage Selector Switch Locking Button Voltage Selector SwitchGenerator Output Voltages Generator AmperageGenerator OUTPUTS/gauge reading How to Read the ac ammeter and ac voltage gaugesAC Voltmeter Gauge Reading AC Ammeter Gauge Reading3Ø-240/139 Uvwo Terminal Output Voltages Uvwo Terminal Output Voltages3Ø-208V/1Ø-120V Uvwo Terminal Output Voltages 1Ø-240/120V Uvwo Terminal Output Voltages 3Ø-480/277V Uvwo Terminal Output VoltagesCircuit Breakers Inspection/SETUPLubrication Oil Fuel CheckOnly use #2 diesel fuel when refueling Refueling ProcedureAir Cleaner Fan Belt Tension Cleaning the RadiatorCoolant Antifreeze/Summer Coolant/ Water Operation in Freezing WeatherBattery Cable Installation BatteryWiring AlternatorBefore Starting Place the engine speed switch in the LOW down positionStarting Starting ManualPre-Heat Lamp Emergency Shutdown Procedure Normal Shutdown ProcedureTo shutdown the generator, use the following procedure OFF/RESET positionGeneral Inspection Air Cleaner MaintenanceAir Cleaner with Dust Indicator Fuel Tank Inspection Fuel AdditionAir Removal Check Oil Level Radiator CleaningReplacing Oil Filter Flushing Out Radiator and Replacing CoolantBattery Charger & Jacket Water Heater Power Connections Trailer Maintenance Trailer MaintenanceCoupler Type of hitch used on the trailer for towing Brakes Brake AdjustmentHydraulic Surge Brakes ActuatorTire Wear/Inflation Tires/Wheels/Lug NutsSuspension Start all wheel lug nuts by hand Lug Nut Torque RequirementsNever use an pneumatic air gun to tighten wheel lug nuts Trailer/Towing Vehicle Wiring Diagram Trailer Wiring DiagramGenerator Wiring Diagram Generator Wiring DiagramEngine Wiring Diagram Engine Wiring DiagramController Wiring Diagram Controller Wiring DiagramSymptom Possible Problem Solution Troubleshooting GeneratorMethod of Operation Troubleshooting Diagnostic lampPage Explanation of Code in Remarks Column To 3 units Suggested Spare PartsQty Description Generator Assy Field Assy Part Name QTY. RemarksFAN Coupling DiskControl box Assy Diagnostic Switch Push Button SwitchSelector Switch Part Name QTY RemarksControl box Assy Switch Cover Switch BracketAlarm Lamp Water Temperature GaugeControl box Assy Wire HARNESS, Engine SWITCH, Fuel PumpEngine and Radiator Assy INDICATOR, AIR Cleaner AIR CleanerBracket AIR Cleaner BAND, AIR CleanerEngine and Radiator Assy AIR Duct Hose ConnectorBlow by Hose Hose JointEngine and Radiator Assy Cooler Hose BRACKET, Inter CoolerFAN Shroud BRACKET, FAN ShroudOutput Terminal Assy Output Terminal Bolt Terminal BoardTerminal Cover Output WindowBattery Assy Battery Sheet BatteryBattery Band Battery Bolt SETMuffler Assy Exhaust Pipe MufflerGasket Bolt SETFuel Tank Assy Fuel Tank CAP Fuel TankFuel Sender Unit Fuel Tank BracketEnclosure ASSY. Part Environmental Tank BaseFront Frame Hose CoverEnclosure ASSY. Part Duct Back PlateOver COVER, Front Frame COVER, Radiator CAPEnclosure ASSY. Part Rear Frame Enclosure ASSY. Part Washer Seal RubberManual Pack Side PanelRubber Seals Assy REMArks Nameplate and Decals Assy Decal Decal NOTICE, Load Sharing FrenchNameplate and Decals Assy Plate MQ Power Decal MQ PowerDecal NOTICE, Supply Wires English Decal NOTICE, Supply Wires FrenchFreIght polICY Terms and Conditions of Sale PartsPage HERE’S HOW to GET Help