General Inspection Prior to Operation
The
Extension Cable
When electric power is to be provided to various tools or loads at some distance from the generator, extension cords are normally used. Cables should be sized to allow for distance in length and amperage so that the voltage drop between the generator and point of use (load) is held to a minimum. Use the Cable Selection Guide (Table 8) for selecting proper cable size.
DCA-500SSK — PRE-SETUP
Circuit Breakers
To protect the generator from an overload, a
NOTE
ALWAYS consult with a licensed electrician for correct extension cord wire size.
Table 10. Cable Selection (60 Hz, Single Phase Operation)
Current | Load In Watts | Maximum Allowable Cable Length | |||||
|
|
|
|
|
| ||
| At |
|
|
|
| ||
in | At 120 |
|
|
|
| ||
Amperes | 240 | #10 Wire | #12 Wire | #14 Wire | #16 Wire | ||
Volts | |||||||
Volts |
|
|
|
| |||
|
|
|
|
|
| ||
|
|
|
|
|
|
| |
2.5 | 300 | 600 | 1000 ft. | 600 ft. | 375 ft. | 250 ft. | |
|
|
|
|
|
|
| |
5 | 600 | 1200 | 500 ft. | 300 ft. | 200 ft. | 125 ft. | |
|
|
|
|
|
|
| |
7.5 | 900 | 1800 | 350 ft. | 200 ft. | 125 ft. | 100 ft. | |
|
|
|
|
|
|
| |
10 | 1200 | 2400 | 250 ft. | 150 ft. | 100 ft. |
| |
|
|
|
|
|
|
| |
15 | 1800 | 3600 | 150 ft. | 100 ft. | 65 ft. |
| |
|
|
|
|
|
|
| |
20 | 2400 | 4800 | 125 ft. | 75 ft. | 50 ft. |
| |
|
|
|
|
|
|
| |
CAUTION: Equipment damage can result from low voltage. |
| ||||||
|
|
|
|
|
|
|
PAGE 44 —