DCA-25USIXF/DCA-25USI2XF— GENERATOR SHUT-DOWN PROCEDURE

Normal Shut-down Procedure

To shutdown the generator, use the following procedure:

1.Switch the MAIN, AUX and GFCI circuit breakers (Figure 53) to the OFF position (no load).

Figure 53. Main, AUX. and GFCI

Circuit Breakers (OFF)

3.Let the engine cool by running it for 3-5 minutes with no load applied (circuit breakers in the OFF position).

4.Place the ignition switch (Figure 54) in the “STOP”position, remove the key and store in a safe place.

Figure 54. Ignition Switch (Off Position)

5.Remove all loads from the generator.

6.Allow for sufficient time for cooling and then inspect the complete unit for any damage or loosening that may have occured during operation.

7.Check the engine oil, coolant and fuel levels. Replenish as necessary.

Emergency Shut-down Procedure

1.To shut-down the engine in the event of an emergency, switch the MAIN, GFCI and LOAD (Figure 53) circuit breakers to OFF position.

2.Turn the ignition switch key to the STOP position (Figure 54).

Automatic Shut-down System

This unit is equipped with safety devices to automatically stop the engine in the event of low oil pressure, approximately 14 psi (97 kPa), or high water temperature, approximately 230° F (110° C). The alarm lamps on the Engine Control Panel illuminate to signify the reason for the shutdown.

CAUTION - AUTOMATIC SHUT-DOWN

After automatic shut-down, ALWAYS inspect the unit and eliminate any problems before attempting to restart. Failure to do so can damage the unit.

Before inspecting, turn the starter switch to the STOP position, place all Generator Circuit Breakers in the OFF position and allow sufficient time for adequate cooling. When ready to restart, complete all steps in the Generator Startup Procedure section of this manual.

Engine protection is furnished

NOTEduring operation, but cannot replace normal preventive maintenance.

Regularly maintain the unit as specified in the Maintenance section of this manual to prevent damage.

DCA-25USIXF/DCA-25USI2XF — OPERATION AND PARTS MANUAL — REV. #1 (05/08/09) — PAGE 37

Image 37
Contents Model DCA-25USIXF Model DCA-25USI2XF DCA-25USIXF/DCA-25USI2XF- Proposition 65WARNING Diesel engine exhaust and someDCA-25USIXF/DCA-25USI2XF-TABLE of Contents Ordering parts has never been easier DCA-25USIXF/DCA-25USI2XF- Parts Ordering ProceduresGenerator Specifications DCA-25USIXF/DCA-25USI2XF- SpecificationsDimensions DCA-25USIXF/DCA-25USI2XF- Dimensions TOP, Side and FrontHazard Symbols DCA-25USIXF/DCA-25USI2XF- Safety Message Alert SymbolsDCA-25USIXF/DCA-25USI2XF- Safety Message Alert Symbols DCA-25USIXF/DCA-25USI2XF- Rules for Safe Operation General SafetyInjury People Carbon monoxide gasDCA-25USIXF/DCA-25USI2XF- Rules for Safe Operation Maintenance SafetyUse well insulated gloves when picking up the battery Battery SafetyDeath Guidelines section in this manual Towing and Transporting SafetyGenerator Decals DCA-25USIXF/DCA-25USI2XF- DecalsDCA-25USIXF/DCA-25USI2XF- Decals Typical Generator Grounding Application DCA-25USIXF/DCA-25USI2XF- InstallationIndoor Installation Outdoor InstallationWhen connecting the generator Mounting Two auxilliary circuit breakers, 250V @50 amps DCA-25USIXF/DCA-25USI2XF- General InformationMajor Components DCA-25USIXF/DCA-25USI2XF- Major ComponentsGenerator Control Panel DCA-25USIXF/DCA-25USI2XF- Generator Control PanelEngine Operating Panel DCA-25USIXF/DCA-25USI2XF- Engine Operating PanelOutput Terminal Panel DCA-25USIXF/DCA-25USI2XF- Output Terminal PanelOutput Terminal Familiarization 120VAC Gfci Receptacles DCA-25USIXF/DCA-25USI2XF- Output Terminal PanelOver Current Relay Connecting LoadsThree Phase Load Single Phase LoadDCA-25USIXF/DCA-25USI2XF- Load APPLICATION/MAXIMUM Motors and motor-drivenDCA-25USI Gauge READING/TERMINAL Panel Connections Voltage Selector SwitchGenerator OutputVoltages Maximum AmpsChange-Over Switch Voltage selector switchDCA-25USI Gauge READING/TERMINAL Panel Connections Reading VoltageUvwo Terminal Output Voltages Three-Phase Position3Ø 240/139 Output Terminal Lug Voltages 3Ø 208V/1Ø120V Output Terminal Lug Voltages1Ø 240V/120V Output Terminal Lug Voltages 3Ø 480/277 Output Terminal Lug VoltagesCircuit Breakers DCA-25USIXF/DCA-25USI2XF- SetupLubrication Oil Fuel CheckRefueling Procedure DCA-25USIXF/DCA-25USI2XF- SetupRefueling Air Cleaner Fan Belt Tension Cleaning the RadiatorOperation FreezingWeather Must be less than 50%Battery Cable Installation BatteryWiring AlternatorBefore Starting DCA-25USIXF/DCA-25USI2XF- Generator START-UP ProcedureEngines exhaust contains harmful emissions Direct exhaust away from nearby personnelIgnition Switch Start Position Oil Pressure Gauge Normal Shut-down Procedure DCA-25USIXF/DCA-25USI2XF- Generator SHUT-DOWN ProcedureEmergency Shut-down Procedure Automatic Shut-down SystemDCA-25USIXF/DCA-25USI2XF- Maintenance DCA-25USIXF/DCA-25USI2XF- Maintenance Brake Adjustment DCA-25USIXF/DCA-25USI2XF-TRAILER MaintenanceBrakes Check the wheel and drum for free rotationTires/Wheels/Lug Nuts DCA-25USIXF/DCA-25USI2XF-TRAILER MaintenanceTireWear/Inflation SuspensionLug Nut Torque Requirements DCA-25USIXF/DCA-25USI2XF-TRAILER MaintenanceStart all wheel lug nuts by hand Trailer/Towing Vehicle Wiring Diagram DCA-25USIXF/DCA-25USI2XF-TRAILERWIRING DiagramEngine Wiring Diagram DCA-25USIXF/DCA-25USI2XF- Enginewiring DiagramDCA-25USIXF/DCA-25USI2XF- Enginewiring Diagram Generator Wiring Diagram DCA-25USIXF/DCA-25USI2XF- Generatorwiring DiagramEngine does not start DCA-25USIXF/DCA-25USI2XF-TROUBLESHOOTING EngineStarter does not run DCA-25USIXF/DCA-25USI2XF-TROUBLESHOOTING Engine Generator Troubleshooting DCA-25USIXF/DCA-25USI2XF-TROUBLESHOOTING GeneratorDCA-25USIXF/DCA-25USI2XF- Explanation of Code in Remarks Sample Parts ListQty Description DCA-25USIXF/DCA-25USI2XF- Suggested Spare PartsDCA-25USIXF/DCA-25USI2XF- Generator Assy DCA-25USIXF/DCA-25USI2XF- Generator Assy DCA-25USIXF- Control BOX Assy DCA-25USIXF- Control BOX Assy DCA-25USIXF- Control BOX Assy DCA-25USIXF- Control BOX Assy DCA-25USI2XF- Control BOX Assy DCA-25USI2XF- Control BOX Assy DCA-25USI2XF- Control BOX Assy DCA-25USI2XF- Control BOX Assy DCA-25USIXF- Engine ANDvRADIATOR Assy DCA-25USIXF- Engine and Radiator Assy DCA-25USIXF- Engine and Radiator Assy M9200200004 M96020000030150000018 0199901600DCA-25USI2XF- Engine and Radiator Assy 8944567412 M1923200124M9200100904 0150000016DCA-25USI2XF- Engine and Radiator Assy M1316100603 Output Terminal Assy DCA-25USIXF/DCA-25USI2XF- Outputterminal AssyM9220000004 M1230700003M9220000104 0039308000DCA-25USIXF/DCA-25USI2XF- Battery Assy M9310500014 0602220185M9103000304 0602220920DCA-25USIXF- Muffler Assy DCA-25USIXF Muffler Assy DCA-25USI2XF- Muffler Assy M1333200304 M1332000512M1333300204 M1333003013DCA-25USIXF/DCA-25USI2XF- Fueltank Assy 0605505072 M13630013020605501098 0605516090DCA-25USIXF- Enclosure Assy M1493000004 M1413002502M1413100003 0603306797 PLUG, 1-1/2 0016910030DCA-25USIXF- Enclosure Assy 27A M1495300504 M144530010327B M1495300604 M1445400103DCA-25USIXF- Enclosure Assy 52A 0030006000 51A C9312500004M9112100504 M1435000903DCA-25USI2XF- Enclosure Assy M1493000704 M1413003902M1413600004 M1423002402DCA-25USI2XF- Enclosure Assy 34A M1493305104 M1443302203M1443400103 35A M1493305204DCA-25USI2XF- Enclosure Assy 59A 0030006000 58A C9312500004M1433300003 M1433001103DCA-25USIXF/DCA-25USI2XF- Rubber Seals Assy 0314500560 02292007900229200630 0228901220DCA-25USIXF/DCA-25USI2XF- Nameplate and Decals Assy DCA-25USIXF/DCA-25USI2XF- Nameplate and Decals Assy Freightpolicy Terms and Conditions of Sale PartsPage Fax 972 Tel