DCA-25USIXF/DCA-25USI2XF— GENERATOR SHUT-DOWN PROCEDURE
Normal Shut-down Procedure
To shutdown the generator, use the following procedure:
1.Switch the MAIN, AUX and GFCI circuit breakers (Figure 53) to the OFF position (no load).
Figure 53. Main, AUX. and GFCI
Circuit Breakers (OFF)
3.Let the engine cool by running it for
4.Place the ignition switch (Figure 54) in the “STOP”position, remove the key and store in a safe place.
Figure 54. Ignition Switch (Off Position)
5.Remove all loads from the generator.
6.Allow for sufficient time for cooling and then inspect the complete unit for any damage or loosening that may have occured during operation.
7.Check the engine oil, coolant and fuel levels. Replenish as necessary.
Emergency Shut-down Procedure
1.To
2.Turn the ignition switch key to the STOP position (Figure 54).
Automatic Shut-down System
This unit is equipped with safety devices to automatically stop the engine in the event of low oil pressure, approximately 14 psi (97 kPa), or high water temperature, approximately 230° F (110° C). The alarm lamps on the Engine Control Panel illuminate to signify the reason for the shutdown.
CAUTION - AUTOMATIC
After automatic
Before inspecting, turn the starter switch to the STOP position, place all Generator Circuit Breakers in the OFF position and allow sufficient time for adequate cooling. When ready to restart, complete all steps in the Generator Startup Procedure section of this manual.
Engine protection is furnished
NOTEduring operation, but cannot replace normal preventive maintenance.
Regularly maintain the unit as specified in the Maintenance section of this manual to prevent damage.