Outdoor Installation

Install the generator in a clear area. Make sure the generator is on secure level ground so that it cannot slide or shift around. Also install the generator in a manner so that the exhaust will not be discharged in the direction of nearby homes.

The installation site must be relatively free from moisture and dust. All electrical equipment should be protected from excessive moisture. Failure to do will result in deterioration of the insulation and will result in short circuits and grounding.

Foreign materials such as dust, sand, lint and abrasive materials have a tendency to cause excessive wear to engine and alternator parts.

CAUTION:

Pay close attention to ventilation when operating the generator inside tunnels and caves. The engine exhaust contains noxious elements. Engine exhaust must be routed to a ventilated area.

Indoor Installation

Exhaust gases from diesel engines are extremely poisonous. Whenever an engine is installed indoors the exhaust fumes must be vented to the outside.The engine should be installed at least two feet from any outside wall. Using an exhaust pipe which is too long or too small can cause excessive back pressure which will cause the engine to heat excessively and possibly burn the valves.

Mounting

The generator must be mounted on a solid foundation (such as concrete) and set firmly on the foundation to isolate vibration of the generator when it is running. The generator must set at least 6 inches above the floor or grade level (in accordance to NFPA 110, Chapter 5-4.1). DO NOT remove the metal skids on the bottom of the generator. They are to resist damage to the bottom of the generator and to maintain alignment.

DCA-45USI — INSTALLATION

Generator Grounding

To guard against electrical shock and possible damage to the equipment, it is important to provide a good EARTH ground.

Article 250 (Grounding) of the National Electrical Code (NEC) provides guide lines for proper grounding and specifies that the cable ground shall be connected to the grounding system of the building as close to the point of cable entry as practical.

NEC articles 250-64(b) and 250-66 set the following grounding requirements:

1.Use one of the following wire types to connect the generator to earth ground.

a.Copper - 10 AWG (5.3 mm2) or larger.

b.Aluminum - 8 AWG (8.4 mm2) or larger.

2.When grounding the generator (Figure 2) connect the ground cable between the lock washer and the nut on the generator and tighten the nut fully. Connect the other end of the ground cable to earth ground.

3.NEC article 250-52(c) specifies that the earth ground rod should be buried aminimum of 8 ft. into the ground.

 

When connecting the generator to

NOTE

any buildings electrical system

ALWAYS consult with a licensed

 

 

electrician.

DCA-45USI — OPERATION AND PARTS MANUAL (STD) — REV. #2 (04/22/05) — PAGE 15

Image 15
Contents DCA-45USI 2 DCA-45USI Operation and Parts Manual STD REV. #2 04/22/05 Wilmington Ave Carson, CA Heres HOW to GET HelpTable of Contents When ordering parts Please supply the following information Parts Ordering ProceduresDCA-45USI Specifications Dimensions DCA-45USI Dimensions Side and FrontFor Your Safety and the Safety of Others DCA-45USI Safety Message Alert SymbolsDCA-45USI Safety Message Alert Symbols DCA-45USI Rules for Safe Operation General SafetyRadiator DCA-45USI Rules for Safe OperationTransporting BatteryEmergencies Towing Safety PrecautionsTypical Generator Grounding Application DCA-45USI InstallationMounting Outdoor InstallationDCA-45USI -TOWING Safety Precautions Explanation of Chart DCA-45USI -TRAILER SpecificationsDCA-45USI Generator Decals DCA-45USI Generator Decals Three auxilliary circuit breakers, @50 amps DCA-45USI General InformationDCA-45USI Major Components Generator Control Panel DCA-45USI Generator Control PanelDCA-45USI Engine Operating Panel Water Temperature Lamp Indicates that the waterFuel FilterWater Level Alarm Lamp This lamp turns Fuel Leak Detected Alarm This indicates that liquidDCA-45USI Output Terminal Panel Familiarization Output Terminal PanelOutput Terminal Familiarization 120VAC Gfci Receptacles DCA-45USI Output Terminal Panel FamiliarizationConnecting Loads Over Current RelayBlower Fan If 3Ø load kVA is not given on Single Phase LoadThree Phase Load DCA-45USI Load ApplicationGenerator OutputVoltages Voltage Selector SwitchVoltage Selector Switch Locking Button Generator AmperageReading Voltage How to Read the OutputTerminal GaugesDCA-45USI Gauge Reading Reading Amperage3Ø 208V/1Ø120V Output Terminal Lug Voltages DCA-45USI Output Terminal Panel ConnectionsUvwo Terminal Output Voltages 3Ø 240/139 Output Terminal Lug Voltages1Ø 240V/120V Output Terminal Lug Voltages 3Ø 480/277 Output Terminal Lug VoltagesFuel Check DCA-45USI PRE-SETUPCircuit Breakers Lubrication OilALWAYS! place trailer on firm level ground before refueling Refueling ProcedureWhen refueling Inhaling fumesOperation Freezing Weather Cleaning the RadiatorAir Cleaner Fan Belt Tension Must be less than 50%Piping and Hose Connection Battery Cable InstallationWiring AlternatorBefore Starting DCA-45USI Generator START-UP ProcedureDCA-45USI Generator START-UP Procedure 38 DCA-45USI Operation and Parts Manual STD REV. #2 04/22/05 Normal Shut-down Procedure Emergency Shut-down ProcedureAutomatic Shut-down System DCA-45USI Maintenance Replacing Fuel Filter Air RemovalCheck Oil Level Replacing Oil FilterHydraulic Surge Brakes DCA-45USI -TRAILER Brakes MaintenanceBrake Adjustment BrakesSuspension DCA-45USI -TRAILER MaintenanceTires/Wheels/Lug Nuts TireWear/InflationStart all wheel lug nuts by hand Lug Nut Torque RequirementsTrailer/Towing Vehicle Wiring Diagram DCA-45USI -TRAILERWIRING DiagramDCA-45USI Enginewiring Diagram DCA-45USI Enginewiring Diagram Generator Wiring Diagram DCA-45USI Generatorwiring DiagramDCA-45USI -TROUBLESHOOTING Generator Items Found In the Items Number Column Explanation of Code in Remarks ColumnQty Description DCA-45USI Suggested Spare PartsDCA-45USI Generator Assy 0042510000 B31101002028051070003 0010310035DCA-45USI Control BOX Assy 0021005080 M12140001020601808825 KAF36110103956 DCA-45USI Operation and Parts Manual STD REV. #2 04/22/05 DCA-45USI Control BOX Assy DCA-45USI Engine and Radiator Assy 0030010000 M1924200014897049-7081 0605000048Engine & Radiator Assy 0602021070 06033002850605511395 0603306395DCA-45USI Outputterminal Assy DCA-45USI Outputterminal Assy DCA-45USI Battery Assy 0602220920 0602220187M9310500014 M9103000304DCA-45USI Muffler Assy 0602320101 M13311001020017112030 M1334000003DCA-45USI Fueltank Assy 0605516090 M13640001020605505070 0605501072DCA-45USI Enclosure Assy DCA-45USI Enclosure Assy 72 DCA-45USI Operation and Parts Manual STD REV. #2 04/22/05 27B 0041216000 26A 004001600026B 0041216000 27A 004001600074 DCA-45USI Operation and Parts Manual STD REV. #2 04/22/05 M1454000503 49A M1494400404M1454000103 50A M1494400104DCA-45USI Rubber Seals Assy 0229400900 02292009500228901385 0228900900DCA-45USI Nameplate and Decals Assy M15000020 M1511400002M1511400102 M1550000204Effective October 1, 2002 Terms and Conditions of Sale Parts DCA-45USI Operation and Parts Manual STD REV. #2 04/22/05 Your Local Dealer is