DCA-45USI — OUTPUT TERMINAL PANEL CONNECTIONS
UVWO Terminal Output Voltages
Various output voltages can be obtained using the using the Output Terminal Lugs. The voltages at the terminals are dependent on the position of the Voltage Selector Switch and the adjustment of the Voltage Regulator Control Knob.
Remember the voltage selector switch determines the range of the output voltage. The voltage regulator (VR) allows the user to increase or decrease the selected voltage.
3Ø 240/139 Output Terminal Lug Voltages
1.Place the voltage selector switch in the 3Ø 240/139 position as shown in Figure 21.
Figure 21. Voltage Selector Switch 240/139V
2.Connect the load wires to the OutputTerminal Lugs as shown in Figure 22.
3Ø 208V/1Ø120V Output Terminal Lug Voltages
1.Place the voltage selector switch in the 3Ø 240/139 position as shown in Figure 24.
Use this position for
Figure 24. Voltage Selector
Switch 3Ø-208V/1Ø-120V
Three-Phase Position
2.Connect the load wires to the OutputTerminal Lugs as shown in Figure 25.
Figure 25. Output Terminal Lugs
3Ø-208V/120V Connections
3.Turn the voltage regulator knob (Figure 23) clockwise to increase voltage output, turn counterclockwise to decrease voltage output.
Figure 22. Output Terminal Lugs
240/139V Three Phase Connections
3. Turn the voltage regulator knob (Figure 23) clockwise to |
|
increase voltage output, turn counterclockwise to | To achieve a 3Ø 208V output, |
decrease voltage output. | |
NOTE | the voltage selector switch |
must be in the 3Ø 240/139V | |
| position and the voltage |
Figure 23. Voltage Regulator Knob | regulator must be adjusted to |
208V. |
PAGE 30 —