Kohler 20EFOZ/24EOZ, 8.5EFOZ, 9EFOZ/10EOZ Circuit Breaker Installation 27EFOZ and 5--32EOZ Models

Page 31

Disabling the generator set. Accidental starting can cause severe injury or death. Before working on the generator set or equipment connected to the set, disable the generator set as follows: (1) Place the generator set start/stop switch in the STOP position. (2) Disconnect the power to the battery charger, if equipped. (3) Remove the battery cables, negative (--) lead first. Reconnect the negative (--) lead last when reconnecting the battery. Follow these precautions to prevent the starting of the generator set by the remote start/stop switch.

WARNING

Hazardous voltage. Moving rotor.

Can cause severe injury or death.

Operate the generator set only when all guards and electrical enclosures are in place.

Grounding electrical equipment. Hazardous voltage can cause severe injury or death. Electrocution is possible whenever electricity is present. Open the main circuit breakers of all power sources before servicing the equipment. Configure the installation to electrically ground the generator set, transfer switch, and related equipment and electrical circuits to comply with applicable codes and standards. Never contact electrical leads or appliances when standing in water or on wet ground because these conditions increase the risk of electrocution.

Short circuits. Hazardous voltage/current can cause severe injury or death. Short circuits can cause bodily injury and/or equipment damage. Do not contact electrical connections with tools or jewelry while making adjustments or repairs. Remove all jewelry before servicing the equipment.

Electrical backfeed to the utility. Hazardous backfeed voltage can cause severe injury or death. Connect the generator set to the building/marina electrical system only through an approved device and after the building/marina main switch is opened. Backfeed connections can cause severe injury or death to utility personnel working on power lines and/or personnel near the work area. Some states and localities prohibit unauthorized connection to the utility electrical system. Install a ship-to-shore transfer switch to prevent interconnection of the generator set power and shore power.

6.2.2Circuit Breaker Installation

(4--27EFOZ and 5--32EOZ Models)

1.Place the generator set start/stop switch in the STOP position.

2.Disconnect the generator set engine starting battery, negative (--) lead first.

3.Remove the controller cover screws and remove the access cover.

4.Remove the screws and nuts to remove the circuit breaker cover plate. Save the mounting hardware.

5.Install the circuit breaker from the inside of the cutout panel and mount it using existing screws removed in step 4. Position the circuit breaker with the ON in the normal upright position or to the left side. Cover the cutout opening, if applicable, with the circuit breaker cover plate. Use existing screws to mount the cover plate.

6.See Section 8 for voltage reconnection.

Note: Kohlerr marine diesel generator sets are fully frequency adjustable and voltage reconnectable. To determine reconnection options, check the model’s specification sheet.

7.Install insulation boots over stator lead terminals if the kit includes insulation boots.

Note: See Section 8 for wiring instructions.

8.Make the recommended connections for the following four reconnection systems using circuit breakers:

Two-pole circuit breaker with a single-voltage system (example: 120-volt, 3-wire). Attach stator leads marked 2 and 4 to the side of the circuit breaker marked LINE. Install the jumper lead across the LINE side of circuit breaker terminals (see Section 8). Attach stator leads 1 and 3 to L0.

Single-pole circuit breaker with a 120-volt, 2-wire, single-voltage system. Attach stator leads marked 2 and 4 to the side of the circuit breaker marked LINE (see Section 8). Attach stator leads 1 and 3 to L0.

Two-pole circuit breaker with a dual-voltage system (example: 120/240-volt, 3-wire). Attach stator leads marked 1 and 4 to the side of the circuit breaker marked LINE. Do not use a jumper lead (see Section 8). Attach stator leads 2 and 3 to L0.

Single-pole circuit breaker with a 240-volt, 2-wire, single-voltage system. Attach the stator lead marked 2 to the side of the circuit breaker marked LINE (see Section 8). Bolt together leads 1 and 4 and tape to insulate from ground. Attach the stator lead marked 3 to L0.

9.Connect the stator lead(s) used for neutral connection to the L0 stud. See the illustrations in Section 8.

TP-6069 6/03

Section 6 Electrical System 21

Image 31
Contents TP-6069 6/03d ModelsPage Table of Contents Page Battery Safety Precautions and InstructionsAccidental Starting Exhaust System Engine Backfire/Flash FireHazardous Noise Fuel SystemHazardous Voltage/ Electrical Shock Hot coolant and steam Can cause severe injury or death Hot PartsMoving Parts VI Safety Precautions and Instructions TP-6069 6/03 Typical Generator Set Location and Mounting IntroductionIntroduction TP-6069 6/03 Location Installation Location ConsiderationsLocation and Mounting General ConsiderationsLocation and Mounting TP-6069 6/03 Intake Through-Hull Strainer Seacock Cover Cooling SystemVentilation Cooling System ComponentsClosed Heat Exchanger 125EFOZ/5--150EOZ Models SeacockSeawater Strainer Water LinesArrow Description 40--150EOZ Models Direct Water-Cooled Cooling System 3.5EFOZ and 4EOZ Models Cooling System TP-6069 6/03 Types Exhaust SystemExhaust Lines Above-Waterline Installation Exhaust System Location, Mounting, and InstallationTypical Above-Waterline Installation 2 Mid/Below-Waterline Installation Typical Mid and Below Waterline Installation Exhaust System TP-6069 6/03 Fuel Tank Fuel SystemFuel Consumption Fuel LinesFuel Filters Fuel Pump LiftCircuit Breaker Considerations Electrical SystemAC Voltage Connections Circuit ProtectionAC Circuit Breaker Ratings 33--150 kW Circuit Breaker Installation 27EFOZ and 5--32EOZ Models Electrical System TP-6069 6/03 Commercial Vessel Installation Regulations Installation In Steel or Aluminum VesselsInstallation Regulations Pleasurecraft Installation RegulationsCCA WiringRemote Start Switch Connection Remote Controller and Harness Options 33--150 kW Models 10 Remote Controller and Harness Options 33--150 kW Models Electrical System TP-6069 6/03 Installation Drawings Installation DrawingsDimension Drawing, 3.5EFOZ/4EOZ Remote Options, 3.5EFOZ/4EOZ Dimension Drawing, 4EFOZ/5EOZ Dimension Drawing, 4EFOZ/5EOZ with Sound Shield Dimension Drawing, 6.5EFOZ/8EOZ Dimension Drawing, 6.5EFOZ/8EOZ with Sound Shield Dimension Drawing, 8.5/9EFOZ and 10EOZ Dimension Drawing, 8.5/9EFOZ and 10EOZ with Sound Shield 10 Dimension Drawing, 11EFOZ/13EOZ 11 Dimension Drawing, 11EFOZ/13EOZ with Sound Shield 12 Dimension Drawing, 11.5/13EFOZ and 14/15.5EOZ ADV-6513B-C 14 Dimension Drawing, 16/17.5EFOZ and 20EOZ ADV-6481B-D 16 Dimension Drawing, 19/20EFOZ and 23/24EOZ ADV-6494B-C 18 Dimension Drawing, 23/27EFOZ and 28/32EOZ ADV-6285B-F 20 Dimension Drawing, 33EFOZ/40EOZ ADV-6581B-E 22 Dimension Drawing, 33EFOZ/40EOZ with Sound Shield 23 Dimension Drawing, 33EFOZ/40EOZ with Electric Clutch 24 Dimension Drawing, 40EFOZ/50EOZ ADV-6582B-E 26 Dimension Drawing, 40EFOZ/50EOZ with Sound Shield 27 Dimension Drawing, 40EFOZ/50EOZ with Electric Clutch 28 Dimension Drawing, 55EFOZ/65EOZ ADV-6583B-E 30 Dimension Drawing, 55EFOZ/65EOZ with Sound Shield 31 Dimension Drawing, 55EFOZ/65EOZ with Electric Clutch 32 Dimension Drawing, 70/80EFOZ and 80/99EOZ ADV-6603B-D ADV-6603C-D ADV-6603D-D 36 Dimension Drawing, 100/125EFOZ and 125/150EOZ ADV-6594B-D ADV-6594C-D Four-Lead Reconnection Reconnection/Adjustments1 100--120-Volt Configurations 2 100--120/200--240-Volt ConfigurationsTwelve-Lead Reconnection 3 200--240-Volt ConfigurationsVoltage Adjustment Overvoltage adjustment potentiometer R41 LED4 red Marine Manual Ship-to-Shore Transfer Switch Stab Voltage Regulator Adjustment 4-27EFOZ and 5-32EOZ Models13 Governor Adjustment 4EFOZ/5EOZ shown Reconnection/Adjustments TP-6069 6/03 Motors Appendix a Generator Selection and Wattage RequirementsAnsi Appendix B AbbreviationsLCB Generator Output Appendix C Generator Set Output Ratings ProcedurePage Page Page 2000, 2001, 2002, and 2003 by Kohler Co. All rights reserved