Kohler 11EFOZ/13EOZ, 8.5EFOZ, 9EFOZ/10EOZ manual Overvoltage adjustment potentiometer R41 LED4 red

Page 80

Short circuits. Hazardous voltage/current can cause severe injury or death. Short circuits can cause bodily injury and/or equipment damage. Do not contact electrical connections with tools or jewelry while making adjustments or repairs. Remove all jewelry before servicing the equipment.

Overvoltage Shutdown Adjustment Procedure

1.Disconnect the generator set engine starting battery, negative (--) lead first. Disconnect power to the battery charger (if equipped).

2.With the generator set shut down, open the output line circuit breaker to disconnect the load from the generator set.

3.Remove the controller cover.

4.Wrap the shaft of an insulated-handle screwdriver with electrical tape to insulate the metal shaft. Turn the overvoltage potentiometer (R41) on the main circuit board fully clockwise. See Figure 8-8.

5.Connect a digital AC voltmeter (or other 1% minimum accuracy voltmeter) to terminals V0 and V7 on the controller terminal block. See Figure 8-6.

6.Reconnect the battery, negative (--) lead last.

7.Start the generator set by placing the generator set master switch in the RUN position.

8.Adjust the output voltage to 115% of the nominal output voltage using the voltage adjustment potentiometer. If the voltage configuration is 139/240 volts (low wye) or 277/480 volts (high wye), 3-phase, 4-wire, 60 Hz, adjust output voltage to 160 volts across terminals V0 and V7. For all other voltages, adjust the output to 140 volts across terminals V0 and V7.

Adjust the voltage using the voltage adjustment potentiometer on the generator controller front panel. See Figure 8-7.

9.Use the insulated screwdriver to slowly rotate the overvoltage adjustment potentiometer (R41) counterclockwise until red LED4 lights. See

Figure 8-8. The generator set should shut down on an overvoltage fault in approximately 2 seconds.

 

1

2

 

R41

 

 

LED4

 

P2

P1

 

 

 

A-336415-A

1.Overvoltage adjustment potentiometer (R41)

2.LED4 (red)

Figure 8-8 Overvoltage Shutdown Adjustment on Main Circuit Board

10.Turn the voltage adjustment potentiometer counterclockwise to prevent overvoltage shutdown upon restart. Restart the generator set. Slowly increase the voltage by turning the voltage adjustment potentiometer clockwise. Verify the shutdown voltage point (115% of the nominal output voltage) by observing the voltmeter and noting when LED4 lights. The generator set should shut down on overvoltage fault in approximately 2 seconds. If the shutdown voltage point is not 115% of nominal voltage, repeat the calibration output procedure; otherwise, continue to step 11.

11.Turn the voltage adjustment potentiometer counterclockwise to prevent overvoltage shutdown upon restart. Restart the generator set. Readjust the generator set output to the nominal voltage using the voltage adjustment potentiometer.

12.Stop the generator set by placing the generator set master switch in the OFF/RESET position. Seal the overvoltage adjustment potentiometer (R41) with RTV sealant or equivalent. Replace the controller cover.

70 Section 8 Reconnection/Adjustments

TP-6069 6/03

Image 80
Contents Models TP-6069 6/03dPage Table of Contents Page Accidental Starting Safety Precautions and InstructionsBattery Engine Backfire/Flash Fire Exhaust SystemHazardous Voltage/ Electrical Shock Fuel SystemHazardous Noise Hot Parts Hot coolant and steam Can cause severe injury or deathMoving Parts VI Safety Precautions and Instructions TP-6069 6/03 Introduction Typical Generator Set Location and MountingIntroduction TP-6069 6/03 Installation Location Considerations Location and MountingGeneral Considerations LocationLocation and Mounting TP-6069 6/03 Cooling System VentilationCooling System Components Intake Through-Hull Strainer Seacock CoverSeacock Seawater StrainerWater Lines Closed Heat Exchanger 125EFOZ/5--150EOZ ModelsArrow Description 40--150EOZ Models Direct Water-Cooled Cooling System 3.5EFOZ and 4EOZ Models Cooling System TP-6069 6/03 Exhaust Lines Exhaust SystemTypes Exhaust System Location, Mounting, and Installation Above-Waterline InstallationTypical Above-Waterline Installation 2 Mid/Below-Waterline Installation Typical Mid and Below Waterline Installation Exhaust System TP-6069 6/03 Fuel System Fuel TankFuel Lines Fuel FiltersFuel Pump Lift Fuel ConsumptionElectrical System AC Voltage ConnectionsCircuit Protection Circuit Breaker ConsiderationsAC Circuit Breaker Ratings 33--150 kW Circuit Breaker Installation 27EFOZ and 5--32EOZ Models Electrical System TP-6069 6/03 Installation In Steel or Aluminum Vessels Installation RegulationsPleasurecraft Installation Regulations Commercial Vessel Installation RegulationsWiring CCARemote Start Switch Connection Remote Controller and Harness Options 33--150 kW Models 10 Remote Controller and Harness Options 33--150 kW Models Electrical System TP-6069 6/03 Installation Drawings Installation DrawingsDimension Drawing, 3.5EFOZ/4EOZ Remote Options, 3.5EFOZ/4EOZ Dimension Drawing, 4EFOZ/5EOZ Dimension Drawing, 4EFOZ/5EOZ with Sound Shield Dimension Drawing, 6.5EFOZ/8EOZ Dimension Drawing, 6.5EFOZ/8EOZ with Sound Shield Dimension Drawing, 8.5/9EFOZ and 10EOZ Dimension Drawing, 8.5/9EFOZ and 10EOZ with Sound Shield 10 Dimension Drawing, 11EFOZ/13EOZ 11 Dimension Drawing, 11EFOZ/13EOZ with Sound Shield 12 Dimension Drawing, 11.5/13EFOZ and 14/15.5EOZ ADV-6513B-C 14 Dimension Drawing, 16/17.5EFOZ and 20EOZ ADV-6481B-D 16 Dimension Drawing, 19/20EFOZ and 23/24EOZ ADV-6494B-C 18 Dimension Drawing, 23/27EFOZ and 28/32EOZ ADV-6285B-F 20 Dimension Drawing, 33EFOZ/40EOZ ADV-6581B-E 22 Dimension Drawing, 33EFOZ/40EOZ with Sound Shield 23 Dimension Drawing, 33EFOZ/40EOZ with Electric Clutch 24 Dimension Drawing, 40EFOZ/50EOZ ADV-6582B-E 26 Dimension Drawing, 40EFOZ/50EOZ with Sound Shield 27 Dimension Drawing, 40EFOZ/50EOZ with Electric Clutch 28 Dimension Drawing, 55EFOZ/65EOZ ADV-6583B-E 30 Dimension Drawing, 55EFOZ/65EOZ with Sound Shield 31 Dimension Drawing, 55EFOZ/65EOZ with Electric Clutch 32 Dimension Drawing, 70/80EFOZ and 80/99EOZ ADV-6603B-D ADV-6603C-D ADV-6603D-D 36 Dimension Drawing, 100/125EFOZ and 125/150EOZ ADV-6594B-D ADV-6594C-D Reconnection/Adjustments 1 100--120-Volt Configurations2 100--120/200--240-Volt Configurations Four-Lead Reconnection3 200--240-Volt Configurations Twelve-Lead ReconnectionVoltage Adjustment Overvoltage adjustment potentiometer R41 LED4 red Marine Manual Ship-to-Shore Transfer Switch Voltage Regulator Adjustment 4-27EFOZ and 5-32EOZ Models Stab13 Governor Adjustment 4EFOZ/5EOZ shown Reconnection/Adjustments TP-6069 6/03 Appendix a Generator Selection and Wattage Requirements MotorsAppendix B Abbreviations AnsiLCB Appendix C Generator Set Output Ratings Procedure Generator OutputPage Page Page 2000, 2001, 2002, and 2003 by Kohler Co. All rights reserved