Note: Position the current transformers with the dot or HI side CT marking toward the generator set.

Note: Only generator sets equipped with AC meter controllers and/or safeguard circuit breakers require CTs.

5.If the controller has meters, remove the controller cover and reposition the meter scale lamp jumper (see Figure 8-6) matching the position of the desired voltage (shown in Figure 8-5).

1

TP-5353-6

1. Lamp Jumper

Figure 8-6 Meter Scale Lamp Jumper

6. The overvoltage shutdown is standard on

Decision-Makert 3+ controllers. The 139/240-volt (low wye) and 277/480-volt (high wye), 3-phase, 4-wire, 60 Hz configurations use different overvoltage shutdown settings than all other configurations. Recalibrate the overvoltage shutdown if the reconnection changes the voltage to or from one of these configurations. See Section 8.3, Decision-Maker 3+ Controller, Overvoltage Shutdown Adjustment. Do not recalibrate the overvoltage adjustment for other voltage changes.

7.If the controller has meters, set the phase selector switch to the L1-L2 position (1-phase or 3-phase configuration depending on generator set connection). Connect a voltmeter across leads L1 and L2 if the controller has no meters.

Note: Equipment damage. Verify that the voltage ratings of the transfer switch, line circuit breakers, and other accessories match the desired line voltage.

8.Reconnect the starting battery, negative (--) lead last. Place the generator set master switch in the RUN position to start the generator set. Observe the voltmeter and verify that the unit has the desired line voltage connection.

Adjust the voltage using the voltage adjustment potentiometer on the generator controller front panel. See Figure 8-7.

9.Stop the generator set after completing the voltage adjustment.

10.Disconnect the external voltmeter if used. Replace the controller cover.

 

 

 

 

 

 

UPPER METER SCALES

 

 

 

 

 

 

1

OFF

3

 

 

 

 

 

 

 

 

 

 

L3

 

 

 

 

 

 

L0--L1

 

 

L3--L1

HERTZ

 

A--C VOLTS

A--C AMPERES

 

L2

 

 

L1

 

 

L1--L2

 

 

L1--L2

 

 

 

 

 

 

L1

AMPS

 

L2

 

 

 

 

 

 

L1--L2

 

L2--L3

 

 

 

 

 

 

 

VOLTS

 

 

 

 

 

 

 

 

LOWER METER SCALES

VOLTAGE

 

S

PREALARM

 

 

 

 

 

 

EMERGENCY

HIGH ENGINE

AUXILIARY

 

AUXILIARY

 

HIGH ENGINE

 

0 0 0 0 0

STOP

O

TEMPERATURE

TEMPERATURE

FAULT

 

PREALARM

TOTAL HOURS

ONLY

 

PREALARM

LOW OIL

 

BATTERY

 

AIR

ADJUST

 

LOW OIL

 

 

 

 

 

PRESSURE

PRESSURE

CHARGER FAULT

DAMPER

 

 

 

LOW WATER

EMERGENCY

LOW BATTERY

SYSTEM

 

 

 

TEMPERATURE

STOP

 

VOLTAGE

 

READY

 

 

 

 

 

 

 

 

GENERATOR

 

 

 

LOW FUEL

OVERSPEED

OVERCRANK

 

SWITCH

 

 

 

 

 

 

 

 

NOT IN AUTO

 

 

BATTERY

 

RUN

OFF/RESET

AUTO

SILENCE

NORMAL

OIL

WATER

 

 

 

 

 

 

ALARM

PRESS

TEMP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LAMP

TEST

 

 

 

1

 

 

 

 

ADV-5849A-

 

 

 

 

 

 

 

 

 

1. Output voltage adjustment potentiometer

 

 

 

 

Figure 8-7 Voltage Adjustment

This is bpid

8.3Decision-Maker 3+ Controller, Overvoltage Shutdown Adjustment

Disconnecting the electrical load. Hazardous voltage can cause severe injury or death. Disconnect the generator set from the load by opening the line circuit breaker or by disconnecting the generator set output leads from the transfer switch and heavily taping the ends of the leads. High voltage transferred to the load during testing may cause personal injury and equipment damage. Do not use the safeguard circuit breaker in place of the line circuit breaker. The safeguard circuit breaker does not disconnect the generator set from the load.

TP-6069 6/03

Section 8 Reconnection/Adjustments 69

Image 79
Contents TP-6069 6/03d ModelsPage Table of Contents Page Battery Safety Precautions and InstructionsAccidental Starting Exhaust System Engine Backfire/Flash FireHazardous Noise Fuel SystemHazardous Voltage/ Electrical Shock Hot coolant and steam Can cause severe injury or death Hot PartsMoving Parts VI Safety Precautions and Instructions TP-6069 6/03 Typical Generator Set Location and Mounting IntroductionIntroduction TP-6069 6/03 Location Installation Location ConsiderationsLocation and Mounting General ConsiderationsLocation and Mounting TP-6069 6/03 Intake Through-Hull Strainer Seacock Cover Cooling SystemVentilation Cooling System ComponentsClosed Heat Exchanger 125EFOZ/5--150EOZ Models SeacockSeawater Strainer Water LinesArrow Description 40--150EOZ Models Direct Water-Cooled Cooling System 3.5EFOZ and 4EOZ Models Cooling System TP-6069 6/03 Types Exhaust SystemExhaust Lines Above-Waterline Installation Exhaust System Location, Mounting, and InstallationTypical Above-Waterline Installation 2 Mid/Below-Waterline Installation Typical Mid and Below Waterline Installation Exhaust System TP-6069 6/03 Fuel Tank Fuel SystemFuel Consumption Fuel LinesFuel Filters Fuel Pump LiftCircuit Breaker Considerations Electrical SystemAC Voltage Connections Circuit ProtectionAC Circuit Breaker Ratings 33--150 kW Circuit Breaker Installation 27EFOZ and 5--32EOZ Models Electrical System TP-6069 6/03 Commercial Vessel Installation Regulations Installation In Steel or Aluminum VesselsInstallation Regulations Pleasurecraft Installation RegulationsCCA WiringRemote Start Switch Connection Remote Controller and Harness Options 33--150 kW Models 10 Remote Controller and Harness Options 33--150 kW Models Electrical System TP-6069 6/03 Installation Drawings Installation DrawingsDimension Drawing, 3.5EFOZ/4EOZ Remote Options, 3.5EFOZ/4EOZ Dimension Drawing, 4EFOZ/5EOZ Dimension Drawing, 4EFOZ/5EOZ with Sound Shield Dimension Drawing, 6.5EFOZ/8EOZ Dimension Drawing, 6.5EFOZ/8EOZ with Sound Shield Dimension Drawing, 8.5/9EFOZ and 10EOZ Dimension Drawing, 8.5/9EFOZ and 10EOZ with Sound Shield 10 Dimension Drawing, 11EFOZ/13EOZ 11 Dimension Drawing, 11EFOZ/13EOZ with Sound Shield 12 Dimension Drawing, 11.5/13EFOZ and 14/15.5EOZ ADV-6513B-C 14 Dimension Drawing, 16/17.5EFOZ and 20EOZ ADV-6481B-D 16 Dimension Drawing, 19/20EFOZ and 23/24EOZ ADV-6494B-C 18 Dimension Drawing, 23/27EFOZ and 28/32EOZ ADV-6285B-F 20 Dimension Drawing, 33EFOZ/40EOZ ADV-6581B-E 22 Dimension Drawing, 33EFOZ/40EOZ with Sound Shield 23 Dimension Drawing, 33EFOZ/40EOZ with Electric Clutch 24 Dimension Drawing, 40EFOZ/50EOZ ADV-6582B-E 26 Dimension Drawing, 40EFOZ/50EOZ with Sound Shield 27 Dimension Drawing, 40EFOZ/50EOZ with Electric Clutch 28 Dimension Drawing, 55EFOZ/65EOZ ADV-6583B-E 30 Dimension Drawing, 55EFOZ/65EOZ with Sound Shield 31 Dimension Drawing, 55EFOZ/65EOZ with Electric Clutch 32 Dimension Drawing, 70/80EFOZ and 80/99EOZ ADV-6603B-D ADV-6603C-D ADV-6603D-D 36 Dimension Drawing, 100/125EFOZ and 125/150EOZ ADV-6594B-D ADV-6594C-D Four-Lead Reconnection Reconnection/Adjustments1 100--120-Volt Configurations 2 100--120/200--240-Volt ConfigurationsTwelve-Lead Reconnection 3 200--240-Volt ConfigurationsVoltage Adjustment Overvoltage adjustment potentiometer R41 LED4 red Marine Manual Ship-to-Shore Transfer Switch Stab Voltage Regulator Adjustment 4-27EFOZ and 5-32EOZ Models13 Governor Adjustment 4EFOZ/5EOZ shown Reconnection/Adjustments TP-6069 6/03 Motors Appendix a Generator Selection and Wattage RequirementsAnsi Appendix B AbbreviationsLCB Generator Output Appendix C Generator Set Output Ratings ProcedurePage Page Page 2000, 2001, 2002, and 2003 by Kohler Co. All rights reserved