Kohler 3.5CFZ, 4CZ, 5CFZ, 6.5CZ installation manual Electrical System

Page 55

Engine (Continued)

Problem

Possible Cause

Corrective Action

Overheats

Improper cooling

Check intake and outlet openings. Check

 

 

coolant level and pressure cap. Check raw

 

 

water strainer.

 

Thermostat defective

Replace

 

Sea strainer clogged

Clean sea strainer

 

Carburetor adjustment too lean

Adjust carburetor mixture

 

Engine ignition timing incorrect

Adjust timing

Unit is noisy

Exhaust system leak

Check exhaust system

 

Exhaust system not securely installed

Check for loose parts

 

Broken or damaged vibromounts

Check vibromounts

 

No installation clearance (unit hits craft

Check clearances

 

structure or compartment)

 

 

No compartment sound insulation

Install approved insulation

 

Excessive vibration engine/ generator

See authorized Kohler service

 

(internal imbalance)

dealer/distributor

 

Loose or vibrating sheet metal

Check shrouds

Electrical System

Problem

Possible Cause

Corrective Action

Battery will not

Loose or corroded connections

Clean and tighten connections

charge

 

 

Sulfated or worn-out battery

Check electrolyte level and specific gravity

 

 

(batteries with filler caps only)

 

Defective battery charging system

Check charging system

 

Battery charging fuse blown

Replace fuse. If fuse blows again see

 

 

authorized Kohler service dealer/distributor

Starter does not

Loose or corroded connections

Clean and tighten loose connections

work properly

 

 

Low battery output

Check electrolyte level and specific gravity

 

 

(batteries with filler caps only). Check

 

 

battery voltage.

 

Defective starter solenoid

Replace starter solenoid

 

Defective start/stop switch

Replace switch

 

Defective wiring

Check wiring

Starter cranks

Low battery output

Check electrolyte level and specific gravity

slowly

 

(batteries with filler caps only)

 

Too heavy viscosity lube oil

Use proper viscosity oil

 

Loose or corroded wiring

Clean and tighten loose connections

 

High starter current draw

Rebuild or replace starter

 

Battery cable undersize

See Installation Section--Electrical

 

 

Systems

TP-5695 12/93

Troubleshooting 4-3

Image 55
Contents 5CZ Marine Generator SetsModels 5CFZCalifornia Proposition Table of Contents Safety Precautions and Instructions Carbon monoxide can cause severe nausea Carbon monoxide Can cause severe nausea, fainting, or deathSulfuric acid in batteries can cause severe injury or Sulfuric acid in batteries Can cause severe injury or deathExplosive fuel vapors can cause severe injury or Explosive fuel vapors Can cause severe injury or deathFlying projectiles can cause severe injury or death Accidental starting Can cause severe injury or deathAccidental starting can cause severe injury or Rotating parts Can cause severe injury or deathHazardous noise Can cause loss of hearing Fire Can cause severe injury or deathSudden backfire can cause severe injury or death Sudden flash fire can cause severe injury or death246242 Pleasure Craft Reference MaterialAdditional References Commercial VesselsPart Description Kohler Part No Routine Service PartsAbbreviation Description Glossary of AbbreviationsNEC Introduction SpecificationsSpecifications General Specifications5CFZ/4CZ 5CFZ/6.5CZ GeneratorGX360EV EngineBPR4HS NGK Accessories Service Views typical Service ViewsPrestart Checks OperationController ControllerStopping StartingCircuit Protection Engine Safety Shutdown SwitchesHigh Water Temperature Shutdown Switch Remote Panels Optional Remote Panel FeaturesRemote Start and Four-Meter Panel Kit Remote Start and Four-Meter FeaturesScheduled Maintenance Or 2 Years Service ScheduleGenerator Lubrication System SpecificationsOil Change/Oil Filter Change Adding OilRemoving Oil Filter Fuel SystemFuel Pump Screen Fuel Pump ScreenCarburetor/Choke Lubrication Carburetor AdjustmentsIgnition System Ignition System ServiceSpark Plugs Carbon fouled Problem Means of Identification Possible Cause NormalGap bridged Oil fouled12. Checking Spark Plug Gap Filling and Checking Cooling Systems- Closed/Heat ExchangerHot coolant and steam Can cause severe injury or death 14. Air-Bleed Screw Flushing and Cleaning TP-5695 12/93 Scheduled Maintenance 17. Removing Anticorrosion Zinc Anticorrosion ZincServicing Mixing Elbow Air Cleaner Mixing ElbowServicing Air Cleaner Pressure CapChecking Specific Gravity BatteryCleaning Checking Electrolyte LevelCharging 21. Specific Gravity Temperature CorrectionValve Adjustment 22. Determining Top Dead Center Governor Governor AdjustmentLubrication Wattage Requirements Generator ServiceGeneral Storage Procedure Not start TroubleshootingEngine Unit cranks but willLacks power Problem Possible Cause Corrective Action Stops suddenlyOperates erratically Electrical System Generator Schematic Wiring Diagram--3.5CFZ, 4CZ, 5CFZ, and 6.5CZ Wiring Diagrams4CZ DiagramsTo Generator To Shore Set Power Wire Generator SetsTo Load 60 Hz LO Neutral GroundLoad Side Line SideWithout Jumper Lead L1--L3Page Generator Selection and Wattage Requirements InstallationMotor Loads Kilowatt Derating Appliance LoadsTypical Location and Mounting Air Requirements CFM L/min Model Combustion Cooling LocationVentilationSpace MountingFuel Supply Fuel SystemsMax. Lift ft. m In. mm Anti-Siphon ProvisionsFuel Lines Fuel Pump Lift Capabilities Fuel Consumption11. Intake Strainer Cooling Systems13. Seawater Strainer Closed/Heat Exchanger15. Closed/Heat Exchanger Cooling System Exhaust SystemsCarbon monoxide 17. Typical Above Waterline InstallationMid/Below Waterline Above WaterlineElectrical Systems Installation in Steel or Aluminum VesselsAC Voltage Connections Wiring BatteryLead Designations Pin Function Remote Start Switch ConnectionSection Dimension Drawing--3.5CFZ, 4CZ, 5CFZ, and 6.5CZStandard on 5CFZ and 6.5CZ Sound Shield--Optional on 3.5CFZ and 4CZParts Ordering Instructions For Sales & Service in U.S.A. & Canada PhoneOperating Hour Service Log Kohler CO. KOHLER, Wisconsin 53044 Phone