isolator or isolation transformer is referenced in ABYC E-8.20 and ABYC E-8.11.

Generator sets installed in commercial vessels are governed by U.S. Coast Guard Regulations, Title 46, the American Bureau of Shipping, and Lloyd’s Register of Shipping. Grounding of equipment is covered in ABS

35.9.6and Lloyd’s Part 6, Chapter 2-1, Section 1.3. The types of permissible neutral grounding of generating equipment are referenced in ABS 35.125 and 35.95.1 and in Lloyd’s Part 6, Chapter 2-1, Section 14.4. Ground fault protection information can be found in Lloyd’s Part 6, Chapter 2-1, Section 14.5 and Part 6, Chapter 2-2, Section 13.6.

Battery

Batteries and their installation must conform to U.S.C.G. Regulations 183.420 (a) through (g). Generator sets should use batteries separate from the propulsion engines whenever possible. Both the generator set and the propulsion engines’starting/charging systems must have a common negative (--) ground.

U.S.C.G Regulation 183.415, Grounding, requires a common conductor to be connected to each grounded cranking motor circuit. This conductor should be sized to match the larger of the engines’two battery cables. (Cable sizes for generator set battery connections are given in Figure 6-20.) This requirement prevents the starting motor current from using alternative electrical paths should the cranking motor ground circuit be restricted or open due to oxidation or loose hardware. These alternative electrical paths include metallic fuel lines which can pose a fire hazard. See Figure 6-21 for battery connections to generator set.

 

 

Cable

 

Distance Between

 

Size

 

At 0°F

(AWG)

At 75°F

Generator Set and

At 32°F

Battery

(--18°C) (0°C)

(24°C)

40 ft. (12.2 m)

00

0

1

30 ft. (9.1 m)

0

1

2

25 ft. (7.6 m)

1

2

4

20 ft. (6.1 m)

2

2

6

15 ft. (4.6 m)

2

4

6

10 ft. (3.0 m)

4

6

8

5 ft. (1.5 m)

6

6

8

2.5 ft. (0.8 m)

8

8

8

Figure 6-20. Battery Cable Sizes

1

2

ADV-5792-D

1. Battery Positive (+)

2. Battery Negative (--)

Connection

Connection

Figure 6-21. Battery Connection Bracket

Wiring

All wiring must be stranded copper. Wire gauges and insulation, conductor temperature ratings, sheath stripping, conductor support and protection, conductor terminals and splices, and overcurrent protection (circuit breakers, fuses) must conform to U.S.C.G. Regulations 183.425 through 183.460. Use rubber grommets and cable ties, as necessary, to protect and secure wiring from sharp objects, exhaust system, and any moving parts.

TP-5695 12/93

Installation 6-13

Image 75
Contents 5CZ Marine Generator SetsModels 5CFZCalifornia Proposition Table of Contents Safety Precautions and Instructions Carbon monoxide can cause severe nausea Carbon monoxide Can cause severe nausea, fainting, or deathSulfuric acid in batteries can cause severe injury or Sulfuric acid in batteries Can cause severe injury or deathExplosive fuel vapors can cause severe injury or Explosive fuel vapors Can cause severe injury or deathFlying projectiles can cause severe injury or death Accidental starting Can cause severe injury or deathAccidental starting can cause severe injury or Rotating parts Can cause severe injury or deathHazardous noise Can cause loss of hearing Fire Can cause severe injury or deathSudden backfire can cause severe injury or death Sudden flash fire can cause severe injury or death246242 Pleasure Craft Reference MaterialAdditional References Commercial VesselsPart Description Kohler Part No Routine Service PartsAbbreviation Description Glossary of AbbreviationsNEC Introduction SpecificationsSpecifications General Specifications5CFZ/4CZ 5CFZ/6.5CZ GeneratorGX360EV EngineBPR4HS NGK Accessories Service Views typical Service ViewsPrestart Checks OperationController ControllerStopping StartingCircuit Protection Engine Safety Shutdown SwitchesHigh Water Temperature Shutdown Switch Remote Panels Optional Remote Panel FeaturesRemote Start and Four-Meter Panel Kit Remote Start and Four-Meter FeaturesScheduled Maintenance Or 2 Years Service ScheduleGenerator Lubrication System SpecificationsOil Change/Oil Filter Change Adding OilRemoving Oil Filter Fuel SystemFuel Pump Screen Fuel Pump ScreenCarburetor/Choke Lubrication Carburetor AdjustmentsIgnition System Service Ignition SystemSpark Plugs Carbon fouled Problem Means of Identification Possible Cause NormalGap bridged Oil fouled12. Checking Spark Plug Gap Cooling Systems- Closed/Heat Exchanger Filling and CheckingHot coolant and steam Can cause severe injury or death 14. Air-Bleed Screw Flushing and Cleaning TP-5695 12/93 Scheduled Maintenance 17. Removing Anticorrosion Zinc Anticorrosion ZincServicing Mixing Elbow Air Cleaner Mixing ElbowServicing Air Cleaner Pressure CapChecking Specific Gravity BatteryCleaning Checking Electrolyte LevelCharging 21. Specific Gravity Temperature CorrectionValve Adjustment 22. Determining Top Dead Center Governor Adjustment GovernorLubrication Generator Service Wattage RequirementsGeneral Storage Procedure Not start TroubleshootingEngine Unit cranks but willProblem Possible Cause Corrective Action Stops suddenly Lacks powerOperates erratically Electrical System Generator Schematic Wiring Diagram--3.5CFZ, 4CZ, 5CFZ, and 6.5CZ Wiring Diagrams4CZ DiagramsWire Generator Sets To Generator To Shore Set PowerTo Load 60 Hz LO Neutral GroundLoad Side Line SideWithout Jumper Lead L1--L3Page Installation Generator Selection and Wattage RequirementsMotor Loads Kilowatt Derating Appliance LoadsTypical Location and Mounting Air Requirements CFM L/min Model Combustion Cooling LocationVentilationSpace MountingFuel Supply Fuel SystemsMax. Lift ft. m In. mm Anti-Siphon ProvisionsFuel Lines Fuel Pump Lift Capabilities Fuel Consumption11. Intake Strainer Cooling Systems13. Seawater Strainer Closed/Heat Exchanger15. Closed/Heat Exchanger Cooling System Exhaust SystemsCarbon monoxide 17. Typical Above Waterline InstallationMid/Below Waterline Above WaterlineInstallation in Steel or Aluminum Vessels Electrical SystemsAC Voltage Connections Wiring BatteryLead Designations Pin Function Remote Start Switch ConnectionSection Dimension Drawing--3.5CFZ, 4CZ, 5CFZ, and 6.5CZStandard on 5CFZ and 6.5CZ Sound Shield--Optional on 3.5CFZ and 4CZParts Ordering Instructions For Sales & Service in U.S.A. & Canada PhoneOperating Hour Service Log Kohler CO. KOHLER, Wisconsin 53044 Phone