76APPENDIX A: SAFETY INFORMATION

urządzenia należy uważnie przeczytać poniższe informacje o bezpieczeństwie.

Power Cord Set—Japan

Important Safety Information

WARNING: Installation and removal of the unit must be carried out by qualified personnel only.

WARNING: If installing the Switch 4200G together (one on top of the other) with SuperStack II or SuperStack 3 units that are shallower than the 4200G, the Switch 4200G unit must be installed below the shallower units.

WARNING: The unit must be earthed (grounded) or must be connected to an earthed power supply to ensure compliance with safety standards.

WARNING: Power Cord Set:

This must be approved for the country where it is used:

U.S.A. and Canada

United Kingdom only

The cord set must be UL-approved and CSA certified.

The minimum specification for the flexible cord is: No. 18 AWG

Type SV or SJ 3-conductor

The cord set must have a rated current capacity of at least 10A.

The attachment plug must be an earth-grounding type with a NEMA 5-15P (15A, 125V) or NEMA 6-15P (15A, 250V) configuration.

The supply plug must comply with BS1363 (3-pin 13 amp) and be fitted with a 5A fuse which complies with BS1362.

The mains cord must be <HAR> or <BASEC> marked and be of type H03VVF3GO.75 (minimum).

Page 76
Image 76
3Com 3CR17661-91 Power Cord Set-Japan Important Safety Information, This must be approved for the country where it is used