Chapter 4 Parameter SettingsDD Series |
| |||||||
|
|
| Settings | 0~10000 (0: No action) |
| |||
| The motor will have current wave motion in some specific area. It can improve this situation by setting | |||||||
| this parameter. (When it is high frequency or run with PG, it can be set to 0. when the current wave | |||||||
| motion happens in the low frequency, please increase the value in |
| ||||||
|
|
|
|
| ||||
|
|
| Accumulative Motor Operation Time (Min.) |
| ||||
Control mode | VF | VFPG | SVC | FOCPG | Factory setting: 0 | |||
|
|
| Settings | 0~1439 |
|
| ||
|
|
| Accumulative Motor Operation Time (day) |
| ||||
Control mode | VF | VFPG | SVC | FOCPG | Factory setting: 0 | |||
|
|
| Settings | 0~65535 |
|
| ||
| This parameter records the motor running time. When | |||||||
| setting to 0. Operation time will not be recorded if it is shorter than 60 sec. |
| ||||||
|
|
|
|
| ||||
|
|
| Maximum Output Frequency |
| ||||
Control mode | VF | VFPG | SVC | FOCPG FOCPM | Factory setting: 50 | |||
|
|
| Settings | 10.00~120.00Hz |
|
This parameter determines the AC motor drive’s Maximum Output Frequency. All the AC motor drive frequency command sources (analog inputs 0 to +10V, 4 to 20mA, 0 to 20mAand ±10V) are scaled to correspond to the output frequency range.
Output Frequency 1(Base frequency /Motor rated frequency)
Control mode VF VFPG SVC FOCPG FOCPMFactory setting: 50
Settings 0.00~120.00Hz
This value should be set according to the rated frequency of the motor as indicated on the motor nameplate. If the motor is 60Hz, the setting should be 60Hz. If the motor is 50Hz, it should be set to 50Hz.
Output Voltage 1(Base voltage/Motor rated voltage)
Control mode VF VFPG SVC FOCPG FOCPM | Factory setting: 220.0 | |
| Settings 0.0V~240.0V |
|
This value should be set according to the rated voltage of the motor as indicated on the motor nameplate. If the motor is 220V, the setting should be 220.0. If the motor is 200V, it should be set to 200.0.
There are many motor types in the market and the power system for each country is also difference. The economic and convenience method to solve this problem is to install the AC motor drive. There is no problem to use with the different voltage and frequency and also can amplify the original characteristic and life of the motor.
Output Frequency 2
Control mode | VF | VFPG | Factory setting: 0.50 | |||
|
|
| Settings | 0.00~120.00Hz |
| |
|
|
| Output Voltage 2 |
| ||
Control mode | VF | VFPG | Factory setting: 5.0 | |||
|
|
| Settings | 0.0V~240.0V |
| |
|
|
|
|
| ||
|
|
| Output Frequency 3 |
| ||
Control mode | VF | VFPG | Factory setting: 0.50 | |||
|
|
|
|
|
|