ADCP-96-015 • Issue 1 • July 2004

ACE-142S

CABINET (FRONT)

HEX BOLTS, FLAT

WASHERS, AND

NUTS (4 PLACES)

 

GROUND

CAPSCREWS, LOCK

SPACER

(ACCESSORY)

WASHERS, AND FLAT

 

WASHERS (4 PLACES)

 

CONCRETE

 

PAD

 

 

19617-B

 

PAD MOUNTING

CABLE

FRAME (PMF)

CONDUIT

 

Figure 10. Mounting the ACE-142S Cabinet on the Concrete Pad

7.Using appropriate lifting equipment, hold the cabinet in position for mounting over the ground spacer or PMF.

8.Lower the cabinet onto the ground spacer or PMF and align the mounting holes in the cabinet base with the threaded holes in the spacer or PMF.

9.If the installation includes a ground spacer, secure the cabinet to the spacer using the four hex bolts, four flat washers and four nuts provided with the spacer. If the installation does not include a ground spacer, secure the cabinet to the PMF using the four hex bolts, lock flat washers, and four flat washers provided with the cabinet. Tighten all fasteners securely.

4.6.2Mounting the ACE-142V Cabinet on a Concrete Pad

Use the following procedures to mount the ACE-142V cabinet on the concrete pad.

1.Remove the plastic plugs that are installed in the threaded corner holes of the PMF and clean off any concrete that may have adhered to the top of the PMF.

Page 19