"UniVert 2" inverter
2.5Description of the SBS
Its electronic
The SBS can be used as the central SBS for parallel operation of up to 8 INVs.
Another outstanding characteristic of the SBS is its communication capability with other systems via integrated interfaces.
The control electronics of the SBS have been designed on the basis of
SBS set
AC
Control unit
DOU
U = 231V
I = 10.3A
SBS
Figure 3 Block diagram of the SBS
The main components of the SBS are (Figure 3):
•Thyristor set
•Control unit
•DOU
Figure 3 illustrates the principle of an SBS.
Load
In normal operation, the SBS is not fired, the load is supplied "Online" by the INV or INVs. If the supply of the load is no longer guaranteed by the INVs or the load voltage has dropped below a permitted value due to a load short circuit, the load is switched over to the mains without interruption.
Apart from power cabling, a bus line is required for the SBS for process control purposes between the INV/INVs and the SBS. The bus line has to be terminated at both ends with a resistor.
Page 15 of 42 | 8000012364 BAL, en |