"UniVert 2" inverter

- Power cables

Burst test in acc. with

 

 

EN 61000-4-4, 2 kV

 

 

Surge test in acc. with

 

 

EN 61000-4-5,

 

 

2 kV asymmetrical

 

- Control cables

Burst test in acc. with

 

 

EN 61000-4-4, 2 kV

 

 

Surge test in acc. with

 

 

EN 61000-4-5,

 

 

2 kV asymmetrical

 

Functional extra-low voltage

With safe isolation at UO 60 V DC

 

to VDE 0100 Part 410 11.83

 

Section 4.3.2

 

Overload behaviour

1.6 x rated current for 1 minute

 

1.3 x rated current for 10 minutes

 

The mains fuse used must be

 

taken into consideration!

Max. load fusing

gL 40A

 

Messages

- Operation

LED green

 

- INV voltage present

LED green

 

- Mains volt. present

LED green

 

- Synchronism

LED green

 

- INV supplies the load LED green

 

- SBS suppl. the load

LED green

 

- Collective fault

LED red

Remote signals (X4)

Collective fault signal via potential-

 

free relay contact X4.1,2,3

 

(safe isolation)

 

 

INV operation signal via potential-

 

free relay contact X4.4,5,6

 

(safe isolation)

 

 

Max. contact load:

 

 

150 V DC < 1.6 A

 

 

Min. contact load: 12 V 0.1 A

Monitoring systems

- Load undervoltage

 

 

- Load overvoltage

 

 

- Mains undervoltage

 

 

- Mains overvoltage

 

 

- Heat sink overtemperature

 

- Mains / INV synchronism

 

- Self-test, watchdog

 

 

- Internal auxiliary voltages

Design

19" mounting rail for installation in

 

module rack in acc. with

 

DIN 41494

 

Page 34 of 42

8000012364 BAL, en

Page 34
Image 34
AEG 8000012364 BAL operating instructions With safe isolation at UO ≤ 60 V DC