"UniVert 2" inverter

Type E-number

G110 E230/10,9/2rfg-CFp2,5

3000000263

Rated output capacity

2.5 kVA

 

 

with power factor

0.8

 

 

Power factor range

0 inductive to 0 capacitive

 

 

Rated output voltage

230 V ±0.5 static, ±3% dynamic at 100% load change

 

 

Output frequency

50 Hz ±0.05%

 

 

THD factor

< 3%

 

 

Rated output current

10.9 A

 

 

DC rated input voltage

110 V -15% ... +20%

 

 

DC rated current

20.4 A at 110 V

 

 

Efficiency

>88%

 

 

DC input current ripple

< 50% of DC rated current

 

 

Monitoring systems

 

 

 

DC undervoltage, switch-off

Fault < 85% of 110 V (93.5 V), without delay

 

Acknowledgement > 103% of 110 V (113.3 V), 15 s delay

 

 

DC overvoltage, switch-off

Fault > 128% of 110 V (140.8 V), without delay

 

Acknowledgement < 125% of 110 V (137 V), 15 s delay

 

 

AC undervoltage, switch-off

Fault < 90% rated (207 V), 2.5 s delay

 

Acknowledgement by ON/OFF switch

 

 

Overtemperature, switch-off

Fault > 80 °C, acknowledgement < 70 °C, approx. 5 s delay

 

 

Page 38 of 42

8000012364 BAL, en

Page 38
Image 38
AEG 8000012364 BAL operating instructions Type E-number G110 E230/10,9/2rfg-CFp2,5 3000000263