AEG 8000012364 BAL ON/OFF Switch, Can Bus Interfaces X6, DIL Switch, S2.1 S2.2 S2.3, INVs

Models: 8000012364 BAL

1 42
Download 42 pages 62.43 Kb
Page 18
Image 18

"UniVert 2" inverter

3.7ON/OFF Switch

The inverter is set ready for operation using the DOU switch on the front panel. The monitoring functions with their respective messages are only active when the inverter is switched on. After switch-off, all faults are acknowledged. The settings of the DIL switches are only accepted if the unit is switched off!

3.8CAN Bus Interfaces X6 / X7

The unit can be controlled and monitored using the 10-pin CAN bus connector X6 if the INV is installed in a power supply cabinet with PSM control unit.

The CAN bus connector X7 has no significance if one inverter in single operation operated without SBS. Both ends of the bus have to be connected to a terminating resistor when several INVs are operated in parallel!

For operation with SBS, only the end of the bus on the INV must have a terminating resistor connected; a bus terminating resistor is integrated in the SBS! (See Figure 1.)

3.9DIL Switch

An 8-pin DIL switch is arranged below the LCD. All settings of / changes to the DIL switch are only activated after the INV has been switched off using the ON/OFF switch. It is counted from the left S2.1 to the right S2.8, switches that are pushed in at the bottom signify "open"! The setting of the switches is shown on the display as a check whenever a change is made; 0 = open; 1 = closed.

Switches S2.1, S2.2 and S2.3: Number of parallel INVs in the system

The settings must be the same on all INVs and the SBS! Standard setting:

1 INV: S2.1, S2.2 and S2.3 open

 

S2.1

S2.2

S2.3

 

 

 

 

1 INV

0

0

0

 

 

 

 

2 INVs

0

0

1

 

 

 

 

3 INVs

0

1

0

 

 

 

 

4 INVs

0

1

1

5 INVs

1

0

0

 

 

 

 

6 INVs

1

0

1

7 INVs

1

1

0

 

 

 

 

8 INVs

1

1

1

Page 18 of 42

8000012364 BAL, en

Page 18
Image 18
AEG 8000012364 BAL operating instructions ON/OFF Switch, Can Bus Interfaces X6, DIL Switch, S2.1 S2.2 S2.3, INVs