AEG 8000012364 BAL operating instructions Disconnection, Parallel INV operation

Models: 8000012364 BAL

1 42
Download 42 pages 62.43 Kb
Page 28
Image 28

"UniVert 2" inverter

Parallel INV operation:

Switch off the INV, switch on miniature circuit-breaker F1

Set the DIL switches

Insert the AC fuses

Connect the DC supply

Switch on all INVs one after the other

(The output contactors K7 of the INVs start at the same time as soon as n-R INV have been switched on)

Connect the load

Individual or parallel operation with SBS

Switch off the INVs, switch on miniature circuit-breaker F1

Set the DIL switches (INV and SBS)

Engage the AC fuses (INV output)

Engage the AC mains and output fuses of the SBS

Disconnect the manual bypass

Connect the load

Connect the DC supply

Switch on all INVs one after the other

(The K7 output contactors of the INVs start at the same time as soon as the last INV has been switched on and the INVs have synchronised to the mains.)

NOTE:

i Before switching on the INVs in parallel operation, or the SBS, make sure the setting of the DIL switches is correct (see chapters 3.9 and 4.11)!

INVs in parallel operation must be set to the same output voltage, to the same number of INVs in the system and to different addresses!

5.4Disconnection

i

Even when switched off, the inverter can still be live due to charged capacitors and external signals. For this reason the terminals must be tested prior to dismantling the unit to ensure that they are de-energised.

The capacitors can be discharged via an external resistor on terminals X2 or X1: L+ and L-.

Switch off the INV

Switch off the AC fuses, if present Switch off the DC supply

Disable interfaces X6, X7, X3 Disconnect earthing

NOTE:

Before switching off an INV in the parallel system, check whether the remaining INVs can take over the entire load. If necessary, the load current must be reduced by switching off individual loads!

Page 28 of 42

8000012364 BAL, en

Page 28
Image 28
AEG 8000012364 BAL operating instructions Disconnection, Parallel INV operation