"UniVert 2" inverter
3.10Signalling, Displays and Remote Signals
The following signals are indicated via LEDs on the front panel:
Display | Colour | Operating status |
Operation | green | INV operation |
UO OK | green | INV output voltage present |
UI< | red | Input voltage < 85% of rated voltage, |
|
| INV has switched off |
UI> | red | Input voltage > 128% of rated voltage, |
|
| INV has switched off |
Fault | red | INV output voltage below 90% of rated |
|
| voltage |
ϑ> | red | Overtemperature on heat sink or |
|
| overload |
Collective | red | Delayed collective fault signal, |
fault |
| delay time 20 s, |
|
| signalling relay is triggered at the same time. |
|
| The following disturbing influences are |
|
| registered: |
|
| INV fault |
|
| UI< |
|
| UI> |
|
| ϑ> |
|
| Overload |
|
| INV output miniature |
|
|
|
The unit is equipped with a
In the event of a fault, the 1st display row shows "FAULT" and the 2nd display row shows the type of fault.
The INV voltage and current values are displayed with three decimals before and one decimal after the decimal point. The display accuracy corresponds to class 1 with respect to the rated output value of the unit.
Remote signalling is carried out by means of
Assignment of the signal terminals:
INV fault:
In the event of a signal, X10.2 – X10.3 or X3.2 – X3.3 close. No fault: X10.2 – X10.1 or X3.2 – X3.1.
When the INV is disconnected from the power supply (no DC supply), a fault is signalled!
The remote signals are designed for safe isolation. The minimum load should not be below 12 V and 0.1 A.
Page 20 of 42 | 8000012364 BAL, en |