AEG 8000012364 BAL operating instructions Electrical Data

Models: 8000012364 BAL

1 42
Download 42 pages 62.43 Kb
Page 36
Image 36

"UniVert 2" inverter

8.3Electrical Data

Type E-number

G48 – 60 E230/14,4/2rfg-CFp3,3

3000000352

G220 E 230/14,4/2rfg-CFp3,3

300000601

Rated output capacity

3.3 kVA

 

 

 

 

 

with power factor

0.8

 

 

 

 

 

Power factor range

0 inductive to 0 capacitive

 

 

 

 

Rated output voltage

230 V ±0.5 static, ±3% dynamic at 100% load connection

 

 

 

 

Output frequency

50 Hz ±0.05%

 

 

 

 

 

THD factor

< 3%

 

 

 

 

 

 

Rated output current

14.4 A

 

14.4 A

 

 

 

 

 

DC rated input voltage

48 V -15% / 60 V +20%

 

220 V -15% +20%

 

 

 

 

 

DC rated current

64 A at 48 V / 51 A at 60 V

 

14 A at 220 V

 

 

 

 

 

Efficiency

> 85%

 

 

> 86%

 

 

 

 

DC input current ripple

< 10% of DC rated current

 

 

 

 

 

Monitoring systems

 

 

 

 

 

 

 

 

DC undervoltage, switch-off

Fault < 85% of 48 V (40.8 V),

 

 

Fault < 85% of 220 V (187 V),

 

without delay

 

 

without delay

 

Acknowledgement > 103% of 48 V

 

 

Acknowledgement > 103% of

 

(49.4 V), 15 s delay

 

 

220 V (226 V), 15 s delay

 

 

 

 

 

DC overvoltage, switch-off

Fault > 128% of 60 V (76.8 V),

 

 

Fault > 128% of 220 V (281 V),

 

without delay

 

 

without delay

 

Acknowledgement < 125% of 60 V

 

 

Acknowledgement < 125% of

 

(75 V), 15 s delay

 

 

220 V (275 V), 15 s delay

 

 

 

 

AC undervoltage, switch-off

Fault < 90% rated (207 V), 2.5 s delay

 

Acknowledgement by ON/OFF switch

 

 

Overtemperature, switch-off

Fault > 80 °C, acknowledgement < 70 °C, approx. 5 s delay

 

 

 

 

 

Page 36 of 42

8000012364 BAL, en

Page 36
Image 36
AEG 8000012364 BAL operating instructions Electrical Data