"UniVert 2" inverter

Type E-number

E230 E230/115/2-VFp26,5-8

3000000646

Rated output capacity

26.5 kVA

 

 

Power loss

< 200 W

 

 

AC rated input voltage

230 V

 

 

AC rated input frequency

50 Hz

 

 

Monitoring systems

 

 

 

AC mains undervoltage,

Fault < 90% nominal (207 V), without delay

blocking of the SBS

Acknowledgement > 90% nominal (211 V)

 

 

 

AC mains overvoltage,

Fault > 110% nominal (253 V), without delay

blocking of the SBS

Acknowledgement < 110% nominal (248 V)

 

 

 

AC load undervoltage,

Fault < 88% nominal (202 V), without delay

switchover to mains

Acknowledgement > 88% nominal (207 V)

 

 

AC load overvoltage, switchover

Fault > 112% nominal (258 V), without delay

to mains

Acknowledgement < 112% nominal (253 V)

 

 

 

Overtemperature, message

Fault > 80°C, acknowledgement < 70°C, 4 s delay

 

self-acknowledging

 

 

Synchronism

Fault phase deviation > 3° el., without delay

INV / SBS circuit

Acknowledgement phase deviation < 2.9° el., 2 s delay

 

 

Page 39 of 42

8000012364 BAL, en

Page 39
Image 39
AEG 8000012364 BAL operating instructions Type E-number E230 E230/115/2-VFp26,5-8 3000000646