AEG 8000012364 BAL Operating modes, Assignment of the signal terminals, Switchover without gap

Models: 8000012364 BAL

1 42
Download 42 pages 62.43 Kb
Page 25
Image 25

"UniVert 2" inverter

With SBS ready:

"U=230.0V"

Load voltage

"

ready"

Operating status

With SBS blocked:

"U=230.0V"

Load voltage

"blocked"

Operating status

With SBS Power Up:

"

"

(nothing displayed)

"PowerUp"

Operating status

With SBS fault:

"

"

(nothing displayed)

"

fault"

Operating status

The busbar voltage and current values are displayed with three decimals before and one decimal after the decimal point. The display accuracy corresponds to class 1 with respect to the rated output value of the unit.

Remote signalling is carried out by means of potential-free contacts via a Combicon connector on the front of the unit.

Assignment of the signal terminals:

SBS fault:

In the event of a signal, X4.2 – X4.3 close, no fault: X4.2 – X4.1

When the SBS is disconnected from the power supply (no mains / INV supply), a fault is signalled!

INV operation:

In the event of a signal, X4.4 – X4.5 close

The remote signals are designed for safe isolation. The minimum load should not be below 12 V and 0.1 A.

4.13Operating modes

Two operating modes can be selected using the DIL switches (see chapter 4.11).

Switchover without gap:

The switchover from INV to SBS is always carried out without interruption. If the INV and SBS circuit are not synchronous, the SBS blocks. If the INV is switched off due to asynchronism or if it fails, the load is not supplied by the SBS.

This operating mode is set ex works and is recommended.

NOTE:

i If the mains are poor or the SBS circuit is supplied by a diesel generator for example, the SBS can be temporarily blocked due to frequency deviations.

Page 25 of 42

8000012364 BAL, en

Page 25
Image 25
AEG 8000012364 BAL operating instructions Operating modes, Assignment of the signal terminals, Switchover without gap