"UniVert 2" inverter
Type
G48 – 60
3000000351
G24
3000000602
Rated output capacity | 1.5 kVA | |||
|
|
|
|
|
with power factor | 0.8 |
| ||
|
|
|
| |
Power factor range | 0 inductive to 0 capacitive | |||
|
|
|
| |
Rated output voltage | 230 V ±0.5 static, ±3% dynamic at 100% load change | |||
|
|
|
| |
Output frequency | 50 Hz ±0.05% | |||
|
|
|
| |
THD factor | < 3% | |||
|
|
|
|
|
Rated output current | 6.5 A |
| 6.5 A | |
|
|
|
|
|
DC rated input voltage | 48 V |
| 24 V | |
|
|
|
|
|
DC rated current | 29 A at 48 V / 23 A at 60 V |
| 62 A at 24 V | |
|
|
|
|
|
Efficiency | > 85% |
|
| > 80% |
|
|
|
| |
DC input current ripple | < 10% of DC rated current | |||
|
|
|
|
|
Monitoring systems |
|
|
|
|
|
|
|
| |
DC undervoltage, | Fault < 85% of 48 V (40.8 V), |
|
| Fault < 85% of 24 V (20.4 V), |
| without delay |
|
| without delay |
| Acknowledgement > 103% of 48 V |
|
| Acknowledgement > 103% of 24 V |
| (49.4 V), 15 s delay |
|
| (24.7 V), 15 s delay |
|
|
|
|
|
DC overvoltage, | Fault > 128% of 60 V (76.8 V), |
|
| Fault > 128% of 24 V (30,7 V), |
| without delay |
|
| without delay |
| Acknowledgement < 125% of 60 V |
|
| Acknowledgement < 125% of 24 V |
| (75 V), 15 s delay |
|
| (30 V), 15 s delay |
AC undervoltage, | Fault < 90% rated (207 V), 2.5 s delay | |||
| Acknowledgement by ON/OFF switch | |||
|
| |||
Overtemperature, | Fault > 80 °C, acknowledgement < 70 °C, approx. 5 s delay | |||
|
|
|
|
|
Page 37 of 42 | 8000012364 BAL, en |