AEG 8000012364 BAL operating instructions Technical Data, General Data INV

Models: 8000012364 BAL

1 42
Download 42 pages 62.43 Kb
Page 31
Image 31

"UniVert 2" inverter

8 Technical Data

8.1General Data INV

DC input current

< rated input current

DC fuse required

gL 80 A with type 3.3 kVA 48 V

 

gL 63 A with type 3.3 kVA 60 V

 

gL 20 A with type 3.3 kVA 220 V

 

gL 80 A with type 1.5 kVA 24 V

 

gL 36 A with type 1.5 kVA 48 V

 

gL 32 A with type 1.5 kVA 60 V

 

gL 25 A with type 2.5 kVA 110 V

Manufacturing and type test

In acc. with DIN 60146 Part 1-1

Emitted interference in acc. with EN 50081-1

- Conducted interference

In acc. with EN 55022 Class "B"

- Emission

In acc. with EN 55022 Class "B"

Noise immunity in acc. with EN 50082-2

- Housing

ESD test to EN 61000-4-2,

 

6 kV contact

 

HF field to EN 61000-4-3,

 

10 V/m (30 MHz – 1 GHz)

- Power cables

Burst test in acc. with

 

EN 61000-4-4, 2 kV

 

Surge test in acc. with

 

EN 61000-4-5,

 

2 kV asymmetrical

- Control cables

Burst test in acc. with

 

EN 61000-4-4, 2 kV

 

Surge test in acc. with

 

EN 61000-4-5,

 

2 kV asymmetrical

Functional extra-low voltage

With safe isolation at UO 60 V DC

 

to VDE 0100 Part 410 11.83

 

Section 4.3.2

Dynamic response

3% with sudden load fluctuations

 

between 0%-100%-0% rated

 

output current

Overload behaviour

1.6 x rated current for 1 minute

 

1.3 x rated current for 10 minutes

Short-circuiting

Continued short-circuit-proof

Page 31 of 42

8000012364 BAL, en

Page 31
Image 31
AEG 8000012364 BAL operating instructions Technical Data, General Data INV