AEG 8000012364 BAL Switches S2.4, S2.5 and S2.6 Own Address INV, S2.4 S2.5 S2.6 Address

Models: 8000012364 BAL

1 42
Download 42 pages 62.43 Kb
Page 19
Image 19

"UniVert 2" inverter

Switches S2.4, S2.5 and S2.6: Own Address (INV)

The settings must be different on all INVs!

Standard setting:

Address 1: S2.4, S2.5 and S2.6 open

 

S2.4

S2.5

S2.6

 

 

 

 

Address 1

0

0

0

Address 2

0

0

1

 

 

 

 

Address 3

0

1

0

Address 4

0

1

1

 

 

 

 

Address 5

1

0

0

 

 

 

 

Address 6

1

0

1

 

 

 

 

Address 7

1

1

0

 

 

 

 

Address 8

1

1

1

 

 

 

 

ATTENTION:

With parallel operation systems, the addresses set must not exceed the number of parallel INVs in the system; for example, in a system with

2 parallel inverters only address 1 or 2 may be set. Addresses 3 or 4 are then only permissible for individually operated INVs!

Switches S2.7 and S2.8: Number of redundant INVs

 

S2.7

S2.8

 

 

 

0 INVs

0

0

 

 

 

1 INV

0

1

 

 

 

2 INVs

1

0

 

 

 

3 INVs

1

1

 

 

 

The settings must be the same on all INVs and the SBS!

Standard setting: S2.7 and S2.8 open

Example: 4 INVs are in the system, at least 3 INVs should run,

i.e. 1 INV is redundant: S2.1=0; S2.2=1; S2.3=1; S2.7=0; S2.8=1