10.3 Repairs
Only AEG PS skilled personnel may carry out repairs and
modifications on the compact station CS.xx.
If you want other personnel to carry out this work, this will need to
be authorised by means of written approval from AEG PS.
Only original AEG PS spare parts (or spare parts purchased from
AEG PS) may be used.
10.3.1 Testing after Repairs
Each time the equipment is repaired or modified, all recurrent
tests/measurements are to be carried out and documented in
accordance with DIN VDE 0105 (initial start-up log) once the work
is complete.
10.3.2 Replacement Work 10.3.2.1 Replacing the Transformer
The transformer can be accessed via the detachable roof or a
door. It can only be replaced when the roof structure has been
removed.
1 2 3 2
Figure 18 - Replacing the transformer, 1 (example)
1 Temperature sensor
2 Internal connections to
MV system
3 Internal connections from
low-voltage box
1. Disconnect the equipment safely.
2. Remove all connections from the transformer, and secure the
equipment.