Compact Station TKS-CS - Operating Instructions
8000043213 BAL Page 19 of 39

7.2 Installation

WARNING
Hinge side of the door when closing
Fingers or hands may be crushed.
Do not hold the hinge side of the door.
Take care while closing the cabinet door.

i Observe the bending radius of the supply lines.
With one bend:
bending radius = 10 x diameter of supply line.

7.2.1 Low-Voltage Box

1
2
3
4
5
Figure 13 - LV box
1 LV box protective cover
2 Load interrupter NH4 - 1250 A
3 Connection panel NH4
(Cu busbars)
4 Cable lug
5 Protective cover

Connection Design *) Torque
(Nm)
L1-3:U, V, W max. 3x240 mm2, M12 2 15.5
PE max. 3x120 mm2, M12 2 15.5
*) 2 = cable lug connection
Table 4 - LV box connections

1. Remove the protective cover from the connection panel.

i
The order of the conductors (L1, L2, L3) must be adhered to.