Compact Station TKS-CS - Operating Instructions
Page 30 of 39 8000043213 BAL
BGV A2 requires the owner to perform repeat tests at stipulated
times in order to verify that the electrical equipment is in perfect
working order.
At stipulated times, the owner must check that the fault current,
differential current and fault voltage protection devices are
functioning properly.
Carry out manual insulation testing.
10.2.5 Care 10.2.5.1 Lubrication
Carry out the following care measures for the station:
Lubricate hinges, rods and guide rails after cleaning.
Lubricate the ball bearings in the axial ventilator after
around 20,000 operating hours or a maximum of 4 years,
according to the manufacturer's specifications.
10.2.5.2 Replacing the Axial Ventilator
WARNING
Rotating parts
Injury to fingers and hands possible.
Do not reach into rotating parts.
De-energise fans.
1 2 3 4 5 6
Figure 17 - Replacing the axial ventilator
1 Housing plate with M9
2 Protective screen
3 Impeller
4 Connection cable with seal
5 Drive motor
6 Weather-proof cover
The axial ventilator must be replaced if it is defective or runs out of
round. As a precaution, it should be changed every 4 years (when
bearing lubrication is due).
Remove the axial ventilator in accordance with the manufacturer's
specifications and send it to the manufacturer for maintenance.