be grounded or the power supply can be operated float- ing at up to a maximum of 240 Volts off ground. Total out- put voltage to ground must not exceed 240 Vdc.

LINE FUSE

 

 

Line Voltage

Fuse

Agilent Part No.

100/115 Vac

2.0 AT

2110-0702

230 Vac

1.0 AT

2110-0457

SPECIFICATIONS

Detailed specifications for the power supply are given in Table

1.All specifications are at front terminals with a resistive load, and local sensing unless otherwise stated. Operating charac- teristics provide useful, but non-warranted information in the form of the nominal performance.

Table 1. Specifications and Operating Characteristics

*AC INPUT

An internal switch permits operation from 100, 115, or 230 Vac lines.

100Vac ± 10%, 47-63 Hz, 163 VA, 125 W

115Vac ± 10%, 47-63 Hz, 163 VA, 125 W

230Vac ± 10%, 47-63 Hz, 163 VA, 125 W

*STABILITY (OUTPUT DRIFT)

Maximum change in output for an 8 hours following a 30 minute warm-up under constant line, load and ambient temperature. Constant Voltage: Less than 0.1% plus 5 mV

Constant Current: Less than 0.1% plus 10 mA

DC OUTPUT

Voltage and current can be programmed via front panel control or remote analog control over the following ranges;

E3614A: 0 - 8 V, 0 - 6 A

E3615A: 0 - 20 V, 0 - 3 A

E3616A: 0 - 35 V, 0 - 1.7 A

E3617A: 0 - 60 V, 0 - 1 A

*OUTPUT TERMINALS

The output terminals are provided on the front and rear panel. They are isolated from the chassis and either the positive or neg- ative terminal may be connected to the ground terminal.

LOAD REGULATION

Constant Voltage - Less than 0.01% plus 2 mV for a full load to no load change in output current.

Constant Current - Less than 0.01% plus 250 μA for a zero to maximum change in output voltage.

LINE REGULATION

Constant Voltage - Less than 0.01% plus 2 mV for any line volt- age change within the input rating.

Constant Current - Less than 0.01% plus 250 μA for any line volt- age change within the input rating.

PARD (Ripple and Noise)

Constant Voltage: Less than 200 μV rms and 1 mV p-p

(20 Hz-20 MHz).

Constant Current: E3614A: Less than 5 mA rms E3615A: Less than 2 mA rms E3616A: Less than 500 μA rms E3617A: Less than 500 μA rms

OPERATING TEMPERATURE RANGE

0 to 40oC for full rated output. Maximum current is derated 1% per degree C at 40oC-55oC.

LOAD TRANSIENT RESPONSE TIME

Less than 50 μsec for output recovery to within 15 mV following a change in output current from full load to half load, or vice versa.

METER ACCURACY: ±(0.5% of output + 2 counts)Bat

 

 

25oC ± 5oC

METER (PROGRAMMING) RESOLUTION

Voltage:

E3614A

10 mV

 

E3615A 10 mV (0 to 20 V), 100 mV (above 20 V)

 

E3616A 10 mV (0 to 20 V), 100 mV (above 20 V)

 

E3617A 10 mV (0 to 20 V), 100 mV (above 20 V)

Current:

E3614A

10 mA

 

E3615A

10 mA

 

E3616A

1 mA

 

E3617A

1 mA

*OVERLOAD PROTECTION

A continuously acting constant current circuit protects the power supply for all overloads including a direct short placed across the terminals in constant voltage operation. The constant voltage cir- cuit limits the output voltage in the constant current mode of oper- ation.

*OVERVOLTAGE PROTECTION

Trip voltage adjustable via front panel control.

E3614A E3615A E3616A E3617A Range: 2.5-10 V 2.5-23 V 2.5-39 V 5-65 V Margin: Minimum setting above output voltage to avoid

false tripping: 4% of output + 2 V for all models

*REMOTE ANALOG VOLTAGE PROGRAMMING (25 ± 5oC)

Remotely varied voltage from 0 to 10 V provides zero to maxi- mum rated output voltage or current.

Voltage: Linearity 0.5% Current: Linearity 0.5%

The programming inputs are protected against input voltages up to ±40 V.

*TEMPERATURE COEFFICIENT

Maximum change in output per oC after a 30-minute warm-up. Constant Voltage: Less than 0.02% plus 500 μV.

Constant Current: E3614A: Less than 0.02% plus 3 mA E3615A: Less than 0.02% plus 1.5 mA E3616A: Less than 0.02% plus 1 mA E3617A: Less than 0.02% plus 0.5 mA

REMOTE SENSING

Meets load-regulation specification when correcting for load-lead drops of up to 0.5 V per lead with sense wire resistance of less than 0.5 ohms per sense lead and lead lengths of less than 5 meters.

1-5

Page 5
Image 5
Agilent Technologies E3617A Line Fuse, AC Input, Stability Output Drift, DC Output, Output Terminals, Load Regulation