Site Preparation

Installation Space Requirements

Clearance for 20.59 in/523 mm Enclosures

(A)

(B)

UPS

 

 

 

 

Conduit Box

 

 

(F)

 

 

(C)

(D)

 

 

 

(G)

 

 

(E)

 

 

 

 

 

 

 

Space requirements

 

in

mm

 

 

 

 

Minimum clearance above Enclosure (A)

 

20.00

508

 

 

 

 

Enclosure depth (B)

 

32.99

838

 

 

 

 

Enclosure width (C)

 

20.59

523

 

 

 

Minimum rear service clearance* (compliant with NEC 110.26 for

36.00

914

North America) (D)

 

 

 

 

 

 

 

Minimum front clearance (E)

 

40.00

1,000

 

 

 

 

Conduit Box, depth (F)

 

3.46

88

 

 

 

No side clearance required (add width of Stabilizing Brackets for

0

0

floor anchoring if applicable)

 

 

 

 

 

 

 

Stabilizing Bracket width

 

3.34

85

 

 

 

Total installation depth, inclusive of Front Panel, Conduit Box and

112.45

2,840

minimum front and rear clearances (G)

 

 

 

 

 

 

 

*) Minimum free rear space for ventilation 4 in/100 mm.

10