Site Preparation – Operating Environment

Minimum breaker settings for 15 kVA UPS

Overload Event

Mains input

Bypass input

Output

Duration

Notes

 

 

 

 

 

 

Internal fault

2.5 kA

2.1 kA

14 kA

<10 ms

1

 

 

 

 

 

 

800% overload bypass

333 A

333 A

500 ms

 

operation

 

 

 

 

 

 

 

 

 

 

 

150% overload normal/

63 A

30 s

 

battery operation

 

 

 

 

 

 

 

 

 

 

 

125% overload normal/

52 A

60 s

 

battery operation

 

 

 

 

 

 

 

 

 

 

 

Continuously

51 A

46 A

46 A

 

 

 

 

 

 

 

Note 1: For the output value, the short-circuit-level is indicated

Minimum breaker settings for 20 kVA UPS

Overload Event

Mains input

Bypass input

Output

Duration

Notes

 

 

 

 

 

 

Internal fault

4 kA

3.4 kA

14 kA

<10 ms

1

 

 

 

 

 

 

800% overload bypass

444 A

444 A

500 ms

 

operation

 

 

 

 

 

 

 

 

 

 

 

150% overload normal/

84 A

30 s

 

battery operation

 

 

 

 

 

 

 

 

 

 

 

125% overload normal/

70 A

60 s

 

battery operation

 

 

 

 

 

 

 

 

 

 

 

Continuously

68 A

62 A

62 A

 

 

 

 

 

 

 

Note 1: For the output value, the short-circuit-level is indicated.

Minimum setting of breakers for 30 kVA UPS

Overload Event

Mains input

Bypass input

Output

Duration

Notes

 

 

 

 

 

 

Internal fault

5 kA

4.2 kA

14 kA

<10 ms

1

 

 

 

 

 

 

800% overload bypass

667 A

667 A

500 ms

 

operation

 

 

 

 

 

 

 

 

 

 

 

150% overload normal/battery

125 A

30 s

 

operation

 

 

 

 

 

 

 

 

 

 

 

125% overload normal/battery

105 A

60 s

 

operation

 

 

 

 

 

 

 

 

 

 

 

Continuously

102 A

92 A

92 A

 

 

 

 

 

 

 

Note 1: For the output value, the short-circuit level is indicated.

14

Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual 990-1598B

Page 20
Image 20
American Power Conversion 208/220 Minimum breaker settings for 15 kVA UPS, Minimum breaker settings for 20 kVA UPS