Communication Wiring to EPO and Optional Equipment
EPO switch must be connected to a NEC Class 2 wiring.
Note
Use only 28-16AWG copper wire for the connection of the Emergency Power Off (EPO) and other optional equipment. Keep all other wiring and uninsulated live parts separate of other NEC Class 2 circuits.
Do not connect any circuits to the EPO terminal block unless it can be confirmed that the circuit is a NEC Class 2 circuit.
990-1598B Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual | 33 |