Loosen the (4) M4 screws (2 each side) from the bottom part of the Conduit Box and remove.
Punch 2 holes in the marked areas of the Conduit Box bottom to fit the size of the conduit pipes, and reattach the Conduit Box bottom to the Enclosure,
Install conduit pipes in the Conduit Box.
Run cables through the conduit pipes and the bottom of the Conduit Box, pull behind the bar and up into the input/output area.
Reinstall the top part of the Conduit Box to the Enclosure, following reverse installation procedures.
Mains input Neutralcables
|
| |
L1 |
|
|
L2 | L3 |
|
| N | Neutral |
|
| N |
| L1 | Output |
|
| |
| L2 | cables |
|
| |
| L3 |
|
|
| cablesGround |
Attach input cable lugs to L1, L2 and L3 input busbars (left side in the UPS – on the front of the busbar), using the provided M6 torx screws. Attach output cable lugs to L1, L2 and L3 output busbars, using the provided M6 torx screws. Attach N x 2 where shown, using the provided torx screws.
Attach Ground x 2 where shown, using the provided torx screws.
Fasten cables with cable ties.
Reinstall rear cover.