Site Preparation – Operating Environment

Recommended phase-conductor sizes [AWG] for a 86°F (30°C) temperature

environment

UPS/AWG sizes

Mains input

AC output

DC input

[AWG]

[AWG]

[AWG], 75°C Wire

 

 

 

 

10 kVA

8

8

1

 

 

 

 

15 kVA

6

6

1

 

 

 

 

20 kVA

4

4

1

 

 

 

 

30 kVA

1

1

1

 

 

 

 

Use Molex lug type or equivalent, and crimp to manufacturer’s specifications.

Note

Cable Size

Cable Lug Type

Crimping Tool

Die

Terminal Bolt

[AWG]

Diameter

 

 

 

 

 

12

YA12CL2TC38

MD7-34R

W12CVT

0.2 in/6 mm

 

 

 

 

 

8

YA8CL2TC38

MD7-34R

W8CVT

0.2 in/6 mm

 

 

 

 

 

6

YA6CL2TC38

MD7-34R

W5CVT

0.2 in/6 mm

 

 

 

 

 

4

YA4CL2TC38

MD7-34R

W4CVT

0.2 in/6 mm

 

 

 

 

 

1

YA1CL2TC38

MD7-34R

W1CVT

0.2 in/6 mm

 

 

 

 

 

WARNING!

At 100% non-liniear load (EN50091-3 standard), the neutral shall be rated for 200% phase current.

EPO switch wiring

The UPS must be connected to either a dry contact or a 24VDC Emergency Power Off (EPO) switch.

See “Pin connections J108 (for EPO wiring options)” on page 37

990-1598B Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual