Floor Anchoring

Note

If floor anchoring is required in your area, read this section. If not, proceed to Operating Environment. However, if you install a 13.85 in/352 mm Enclosure, it must always be equipped with the Stabilizing Bracket for enhanced stability (not necessary to bolt the Stabilizing Bracket to the floor in non-seismic areas).

Drilling floor holes for floor anchoring

Note

If the UPS installation requires floor anchoring, the UPS installation must be anchored to the floor, re-using the brackets that also secured the UPS to the pallets when shipped. For easy determination of where to drill the holes, refer to the applicable drawings below indicating hole positions and size.

Hole positions for floor anchors (stand-alone Enclosures)

Rear

Rear

5.78in/

147mm

5.11in/

130mm

5.11in/

130mm

5.11in/

130mm

5.11in/

130mm

5.11in/

130mm

0.92in/

23.5mm

Floor anchor holes:

Floor anchor holes:

Ø 10 mm

Ø 10 mm

 

 

20.59 in/523 mm Enclosure

25in/650mm

13.85 in/352 mm

 

 

Enclosure

26.3in/575mm

 

 

 

15.9in/404mm

 

 

Refer to this drawing for floor anchor positions for 20.59 in/523 mm.

Refer to this drawing for 13.85 in/352 mm.