Operating Environment

Operating conditions

Install the UPS in an indoor, temperature-controlled area, free of conductive contaminants.

Note

Temperature

Range:

32° to 104°F /

0° to 40°C

Keep Ventilated

Front-to-Rear Airflow (see space considerations)

Relative

Humidity: <95%

Non-condensing

No Conductive

Dust or

Corrosive

Fumes

Altitude derating table:

3,000 ft/914 m: 100% load

4,500 ft/1371 m: 95% load

6,000 ft/1828 m: 91% load

8,000 ft/2438 m: 86% load

10,000 ft/3048 m: 82% load

Heat dissipation

 

BTU/hr at fully

 

BTU/hr at fully

UPS size

charged batteries

UPS size

charged batteries

 

 

 

 

10 kVA

1,774

20 kVA

3,624

 

 

 

 

15 kVA

2,866

30 kVA

5,486

 

 

 

 

Audible noise

UPS Sizes

Audible noise at 100% load

Audible noise at <70% load

(1.09 yard/1 m from the UPS)

(1.09 yard/1 m from the UPS)

 

 

 

10-15 kVA

54 dBA

45.4 dBA

 

 

 

20-30 kVA

58 dBA

48.5 dBA

 

 

 

12

Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual 990-1598B

Page 18